Before Installation - Honeywell JADE W7220 Installation Instructions And Operators Manual

Economizer module
Hide thumbs Also See for JADE W7220:
Table of Contents

Advertisement

Dimensions (See Fig. 1 on page 3):
Height: 4.98 inches (126.4 mm)
Width: 6.3 inches (160 mm)
Depth: 1.34 inches (34 mm)
Weight: 0.58 lb. (0.265 kg)
Approvals: UL listed (XAPX) for USA and Canada;
California Energy Commission (CEC) FDD ID number
HJW10.
4-63/64
(126)
MOUNTING HOLE (X2)
Fig. 1. Dimensions in inches (mm) showing mounting
Accessories
50048926-001 2-pin edge connector for sensors
(20 pieces per bag)
50048926-002 6-pin edge connector for field wir-
ing (20 pieces per bag)
C7250A 20k sensor for MA or OA (dry bulb change-
over)
C7400S Sylkbus sensor for enthalpy control in OA
and/or RA and RA for differential dry bulb change-
over
W7220 PCMOD interface tool for JADE controller
and Personal Computer. For the software, go to
www.customer.honeywell.com/economizertools
50053060-001 Duct mounting kit for sensors
C7632 or C7232 CO
Sylk bus CO
sensor
2

BEFORE INSTALLATION

Review the "Specifications" on page 2 before installing the
The JADE™ Economizer System.
When Installing This Product
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard-
ous condition.
2. Check ratings given in instructions and on the
product to ensure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
6-19/64 (160)
3-5/32 (80)
M32273A
holes.
analog sensors OR one TR40
2
NOTE: Jade will be in the "set up" mode for the first 60
minutes after powered. If a sensor for OA air or
Sylkbus device (sensor, actuator) is disconnected
during the set up mode, the Jade will not alarm
that failure. The MA sensor is a system "critical"
sensor, if the MA sensor is removed during the set
up mode, the Jade will alarm. After 60 minutes the
Jade controller will change to operation mode
and all components removed or failed will alarm
in the operation mode.
INSTALLATION AND SETUP
The following installation procedures should be
performed in the order listed:
1. Mounting — see page 3.
2. Wiring — see page 4.
3. Interface and Programming overview – see page 18.
4. Setup and Configuration — see page 18
5. Checkout — see page 31.
Troubleshooting and Alarms—see page 32.
MOUNTING
This section describes the mounting procedures for the
JADE™ Economizer module and the sensors.
Economizer Module Location and
Mounting
IMPORTANT
Avoid mounting in areas where acid fumes or other
deteriorating vapors can attack the metal parts of
the module's circuit board, or in areas where
escaping gas or other explosive vapors are
present.
IMPORTANT
The module must be mounted in a position that
allows clearance for wiring, servicing, and removal.
Mount the Economizer module on any convenient interior
location using the two mounting holes provided on the
enclosure using #6 or #8 screws (screws are not provided
and must be obtained separately). Use the dimensions in
Fig. 1 on page 3 as a guide.
The Economizer module may be mounted in any
orientation. However, mounting in the orientation shown
in Fig. 1 on page 3 permits proper viewing of the LCD
display and use of the keypad.
Sensor Location and Mounting
The JADE™ Economizer W7220 uses digital and
communicating sensors for control. The C7250
temperature sensors (MA
a
MA = Mixed Air
b
OA = Outdoor Air
3
JADE™ ECONOMIZER MODULE
a
b
and OA
) are 20k NTC. A MA
63-2700—11