2200 series and 3200 series relative humidity and temperature room units

Advertisement

Quick Links

Series 2200 and 3200 Relative Humidity
and Temperature Room Units

Product Description

These room units measure relative humidity and
temperature in the occupied space in which they are
installed. Models with display allow users to view the
measured temperature value. A version with
temperature setpoint adjustment is also offered.
The effective sensing range is 32°F to 122°F (0°C to
50°C), and the setpoint range is 55°F to 95°F (13°C
to 35°C). The humidity measuring range is 0 to
100% RH.
Hardware is included for installation on drywall or on
a 2" × 4" electrical box.
Product Numbers
QFA3212.FWxN
QFA3212.EWxN
QFA3232.EWxN
Accessories
AQA2200-INTL
Room Unit Back Plate
(10-pack)
563-102 GSKT KIT
Room Sensor Insulating
Gasket (10-pack)
(For hollow wall installations)
Caution Notations
CAUTION
Item Number 129-104, Rev. JA
QFA32SS.FWxN
QFA32SS.EWxN
Equipment damage or loss of
data may occur if you do not
follow a procedure as
specified.
Installation Instructions
Expected Installation Time
20 minutes
Required Tools
·
Sizes 1 and 2 Phillips screwdrivers
·
Small and medium flat-blade screwdrivers
·
1/16-inch hex key
·
Medium-duty electric drill
·
3/16-inch (4.8 mm) drill bit
·
One-inch (25 mm) hole saw
·
Small level
·
Tape measure
·
Marker or pencil
Prerequisites
·
Review these instructions before beginning.
·
Installed: appropriate field wiring within the
maximum wiring run length for the individual
equipment controller. The maximum
recommended length is 750 feet (229 m) for
18 AWG; 300 feet (91 m) for 22 AWG.
·
All wiring must comply with National Electric
Code (NEC) and local regulations.
Figure 1. Typical Temperature Room Unit.
Document No. 129-104
December 11, 2017
Page 1 of 4

Advertisement

loading

Summary of Contents for Siemens QFA3212.FWxN

  • Page 1: Product Description

    Hardware is included for installation on drywall or on One-inch (25 mm) hole saw a 2” × 4” electrical box. · Small level · Tape measure Product Numbers · Marker or pencil QFA3212.FWxN QFA32SS.FWxN Prerequisites QFA3212.EWxN QFA32SS.EWxN QFA3232.EWxN · Review these instructions before beginning. Accessories ·...
  • Page 2 (see Figure 6). *Insulating gaskets are sold in 10-packs NOTE: See Figure 2 for details on optional Gasket (Part Number 563-102 GSKT KIT). application. Figure 3. Drywall Mounting (No Rough-in), Typical. Page 2 of 4 Siemens Industry, Inc.
  • Page 3 Document No. 129-104 Installation Instructions December 11, 2017 7. Terminate the wires to the termination blocks on the room unit's base plate. (See Figure 6.) 8. Feed the extra cable back through the hole. Unit Set-up Figure 5. Changing Display to °C. 3.
  • Page 4 Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. APOGEE is a registered trademark or Siemens Industry, Inc. Other product or company names mentioned herein may be the trademarks of their respective owners.

This manual is also suitable for:

Qfa32ss.fwxnFa3212.ewxnQfa32ss.ewxnFa3232.ewxn