Input/Output - ABB ControlMaster CM30 User Manual

Universal process controllers
Hide thumbs Also See for ControlMaster CM30:
Table of Contents

Advertisement

ControlMaster CM30, CM50 and CMF310
Universal process controllers,

7.3 Input/Output

Menu
Input/Output
Exit
Select
Analog Inputs
Analog Input 1 (4)*
Input Type
Digital Volt Free
Freq. Input
Pulse Input
Elect. Low
Elect. High
Linearizer
Eng Units
Eng. Dps
*Analog Inputs 2 to 4: Freq Input, Pulse Input and Resistance not available. A Thermocouple input type can be set only if the first input is set
to Thermocouple.
42
1
1
/
,
/
DIN and fieldmount
4
2
Enables analog and digital inputs / outputs and relays to be configured.
Millivolts, Milliamps, Volts, Resistance (Ohms), RTD, Thermocouple, Digital volt-free,
24V Digital, Freq. Input, Pulse Input.
Additional Input Type comments:
Acts as a digital input.
Sets the maximum frequency and equivalent flow rate in the engineering range 0
to 6000 Hz. (A frequency of 0.01 to 6 KHz can be used to create an analog value.)
This parameter counts pulses and is recommended only for use with electromagnetic
flowmeters.
Sets the required electrical range.
Note. Applicable only to Millivolts, Milliamps, Volts and Ohms.
Linear Inputs
Millivolts
Milliamps
Volts
Resistance  (low)
Resistance  (high)
Sets the required electrical range.
Note. Applicable only to Millivolts, Milliamps, Volts and Freq. Input.
Selects the linearizer type required to condition the input signal.
Notes. For thermocouple applications using an external fixed cold junction, set
Input Type to Millivolts and select the appropriate linearizer type.
Not applicable for Pulse Input, Digital volt-free, 24V Digital parameters.
The selected units are used by the linearizer and displayed in the Operator pages.
Not applicable for: Pulse Input, Digital volt-free, 24V Digital parameters.
Thermocouple and RTD inputs are restricted to deg C, deg F, Kelvin –
see Appendix C, page 108 for analog input (engineering) units.
Engineering decimal places – selects the resolution required to be displayed
for the input value.
Standard Analog Input
0 to 150 mV
0 to 45 mA (CM30 & CMF310)
0 to 50 mA (CM50)
0 to 25 V
0 to 550 
0 to 10 k
7 Advanced Level
Accuracy (% of Reading)
0.1 % or ±20 µV
0.2 % or ±4 µV
0.2 % or ±1 mV
0.2 % or ±0.1 
0.1 % or ±0.5 