• DO NOT terminate near soffit vents or crawl space or other area where condensate or vapor could create a nuisance
hazard or cause property damage.
• DO NOT locate the exhaust vent terminal where condensate or vapor could cause damage or could be detrimental to
the operation of regulators, relief valves, or other equipment.
• DO NOT locate the exhaust vent terminal over public area or walkways where condensate or vapor can cause nui-
sance or hazard.
• DO NOT locate the vent terminal in proximity to plants/shrubs.
VENT INSTALLATION – Before proceeding, make
certain you understand the procedure and cautions
covered in the section "Joining Pipes and Fittings."
POWER VENT INSTALLATION:
Power venting is where the indoor air is used and
the exhaust is vented to the outside. Venting may be
run horizontally through an outside wall or vertically
through a roof through using either 2" (5.1 cm), 3"
(7.6 cm), 4" (10.2 cm) or 6" (15.2 cm) diameter PVC,
ABS or CPVC. This water heater is supplied with a
screened intake elbow and exhaust coupling referred
to as the air intake terminal and the exhaust vent
terminal.
NOTE:
Flexible PP vent kit is available for Power Vent con-
figurations, in either 3" or 4" diameters. These kits
should be used for vertical venting only.
NOTICE: Use of PVC cellular core (ASTM-F891),
ABS Schedule 40, DWV cellular core (ASTM –F628),
or Radel® (polyphenylsulfone) in non-metallic
venting systems is prohibited.
Installation
In a horizontal application, it is important that
condensate not be allowed to buildup in the exhaust
vent pipe. To prevent this from happening, the pipe
should be installed with a slight upward slope of ¼"
per foot. The vent system must be supported every 5
feet of vertical run and every 3 feet of horizontal run
of vent pipe length.
Failure to properly support the vent piping with
hangers and clamps may result in damage to the
water heater or venting system.