Power Requirements And Consumption - Nvidia Quadro VCA Installation Manual

Visual computing appliance
Hide thumbs Also See for Quadro VCA:
Table of Contents

Advertisement

. Hardware
Alert modes
A blue LED identifies the system using the Intelligent Platform Management Interface
(IPMI).
A red LED indicates a hardware error such as a power failure, fan failure, or overheat-
ing.
Color
Alert LED Behavior
Blue
Off
Red
Off
Blue
Blink
Red
Solid
Red
1 blink per second
Red
4 blinks per second
. .

Power requirements and consumption

There are 4x 1600W redundant power supplies. The power supplies can accept either 110V
(ac) or 240V (ac) input.
With all system resources under full load, the maximum power consumption is 2800W (at an
ambient temperature of 35 C). Idle power consumption is 350W (at an ambient temperature
of 25 C).
The following table identifies valid power configurations:
Max input
Number of working
power per
power supplies
power
supply
4 (Normal mode)
700W
3 (1 failed supply)
933W
2 (2 failed supplies)
1400W
The minimal requirements for a VCA are two 120V/20A circuits with two power supplies per
circuit. If any single power supply fails, the system will continue to operate at full load.
A circuit overload can occur when:
One whole circuit fails; or
Two power supplies on the same circuit fail.
With a maximum of two failed power supplies, a single 240V/20A circuit will support the
VCA running at full load. However, a fully redundant system requires two separate 240V/20A
curcuits with two power supplies per circuit; this configuration can tolerate the loss of any
two power supplies or one complete 240V/20A circuit.
©
NVIDIA Corporation NVIDIA Quadro Visual Computing Appliance — Installation Guide
Status Description
Normal mode operation
Normal mode operation
On when enabled by administrator
System component overheat
Power module failure
System fan failure
Max current draw per
power supply (amps at
2800W and 35C)
Dual 120V/20A
120V
240V
circuits; 2 power
supplies per circuit
5.8A
2.9A
7.8A
3.9A
11.7A
5.8A
(overloaded circuit)
Quadro VCA specification
Worst case maximum current draw per circuit
(amps at 2800W and 35C)
Single 240V/20A circuit;
all power supplies on
same circuit
11.7A
11.7A
15.6A
11.7A
23.7A
11.7A
Dual 240V/20A
circuits; 2 power
supplies per circuit
5.8A
7.8A
11.7A

Advertisement

Table of Contents
loading