6. Mounting the PIR Occupancy Sensor
The sensor head is designed to be installed in plasterboard ceiling or ceiling tiles with a thickness of 10mm -
16mm thickness. A 52mm diameter cut-out is required to recess mount the sensor head. The diagram below
shows a cross section through the sensor head. A cut-out template is provided on the sensor box for ease of
making the cut-out.
Minimum 10mm
plaster board
Note: Avoid placing the sensor in positions close to hot or cold air vents and where the field of view extends
through doorways. This will reduce the risk of false triggering of the sensor.
7. Connecting the PIR Occupancy Sensor to a RAPIX eHub
The PIR Occupancy Sensor is only suitable for use with the RAPIX eHub.
The PIR Occupancy Sensor can be connected and powered from one of the two eHub sensor inputs.
A sensor patch lead is provided and is connected to the eHub as shown below.