4-4. FIXING HORIZONTAL VANE
Horizontal vane of each air outlet can be fixed according to the environment where it is installed.
Setting procedures
1) Turn off a main power supply (Turn off a breaker).
2) Disconnect the vane motor connector of the direction of the arrow with pressing the unlocking button as shown in figure
below.
Insulate the disconnected connector with the plastic tape.
Horizontal vane
3) Set the vertical vane of the air outlet by hand slowly within the range in the table below.
Measured standard
position of the grille
<Set range>
Angle θ = 21°
Standard of
horizontal position
(Horizontal)
Dimension A (mm)
Note: Dimension between 39 mm and 49 mm can be arbitrarily set.
Caution
Do not set the dimension out of the range.
.
Erroneous setting could cause dew drips or malfunction of unit.
OCH617
Vane motor
A
A
Angle θ = 24°
39
41
Connector
θ
Horizontal vane
Angle θ = 39°
Angle θ = 42°
47
48
14
Vane motor
Unlocking button
Angle θ = 45°
(Downward)
49