Indication LEDs

The relay is provided with three indication LEDs (green, yellow and red). With
latching/non-latching, steady/blinking light the LEDs indicate different states and
operations of the relay. For more information, see

Alarm LEDs

The relay is provided with eight alarm LED indicators (red). With latching/non-
latching or steady/blinking light the alarm LEDs indicate different states and
operations of the relay. The user can freely enable and disable the predefined alarms.
By default, all the alarms are disabled. To enable alarms, do the following:
1. Select a mode (Control\ALARM#\Control setting\Object mode)
for function blocks MMIALAR1-8 (these are uninitialized by default). The
mode you selected affects the behaviour of the alarms coming to a certain LED.
MMIALAR1 affects LED1, MMIALAR2 affects LED2, and so on. Three alarm
modes are supported regarding latching: non-latched, latched with steady LED,
and latched with blinking LED. For more information about MMIALAR
function blocks, see
"Related documents" on page 7).
2. Enable the alarms by setting the bitmask for the LED
(Configuration\Alarm LEDs\LED1, LED2...)
The alarms can be acknowledged (cleared) from the main view by pressing the [C]
button for 2 s. This acknowledges all the alarms.
For a certain MMIALAR function block, the alarms can also be acknowledged by
selecting "Acknowledge" for parameter Alarm ack
(
Control\ALARM#\Control setting\Alarm ack
alarm(s) only for the corresponding LEDs. After the acknowledgement, the status of
a certain LED (off/steady/blinking) depends on the selected mode and whether the
alarm is still active or not.
After an auxiliary supply break, the state of the alarm LEDs is
!
restored to the same state as before the break. This means that
alarms will be seen even if the alarm went off during the break and
regardless of the mode. The alarms can be acknowledged (cleared)
only from the main view by pressing the [C] button for 2 seconds.
Special features of alarm LEDs
It is also possible to activate alarm LEDs by writing to parameter Alarm LED
states from HMI, or by using serial communication. This works even if the
alarms are not enabled (enabling alarms, see "Alarm LEDs" on page 41). The value
written to that parameter is then logically combined together (by an OR function)
with alarms enabled as described in the previous section.
The actual state of the alarm LEDs can also be read from the parameter Alarm LED
states by using serial communication, or by reading the state from HMI
(Configuration\Display\Alarm LED states).
Technical Reference Manual, Standard Configurations
REX 521
.
Operator's Manual
). This acknowledges