Digital time switch

Advertisement

Quick Links

http://waterheatertimer.org/How-to-wire-GE-15136-timer.html
Digital Time Switch
GE 15136 Timer
APPLICATION
This digital GE Time Switch (15132) is a universal, electromechanical time
switch which can be field configured for various power supply voltages.
The voltage options include 120VAC, 208/240VAC and 277VAC – all within
the same unit! Selection of the desired supply voltage is easily achieved
by positioning dipswitches on the printed circuit board assembly (consult
Dipswitches Configuration on back). The mechanism is mounted in a NEMA
indoor or outdoor enclosure and is intended for the control of lighting, heating,
air conditioning, pumps, motors, or general electrical circuits in residential,
commercial, industrial and agricultural facilities.
SPECIFICATIONS
Input Voltage: 120 VAC, 208/240 VAC, or 277 VAC in all units based
upon dipswitch configuration.
15087
NEMA 3R Indoor & Outdoor BM-A301US5-O2
15207
NEMA 1
Indoor
56922
NEMA 1
Indoor
15132
NEMA 3R Indoor & Outdoor EM-A301US9-O2
15136
NEMA 3R Indoor & Outdoor
Switch Rating: DPDT Models
Normally Open Contacts
40A Resistive, 120-277Vac.
30A General Purpose, 120-277Vac.
20A Resistive, 30Vdc
1 HP, 120Vac ; 2HP, 240Vac ;
20A Ballast, 120-277Vac.
15A Tungsten, 120Vac
5.4A Tungsten, 208-277Vac.
800VA, Pilot Duty, 120Vac.
720VA, Pilot Duty, 240-277Vac.
TV-5, 120Vac
Normally Closed Contacts
30A Resistive, 120-277Vac
15A General Purpose, 120-277Vac
15A Resistive, 30Vdc
20A Ballast, 120-277Vac
1/4HP, 120Vac; 1/2HP, 208-240Vac.
290VA, Pilot, 120Vac.
360VA, Pilot, 208-240Vac.
NOTE: If loads are connected to both NC and NO contacts, both contacts are
decorated to 67% of the above values.
ENVIRONMENTAL RATINGS
Ambient Temperature: –40F to 130F
Humidity: 0-95% RH, Non-condensing
WIRING CONNECTIONS
Screw clamp terminals for up to 2 AWG #8 wires per position. For supply
connections, use 8AWG or larger wires suitable for at least 105° C. Use copper
conductors only.
Lights
Power LED (Orange)
– Light illuminates when power is applied to
the timer
Status LED (Green)
– Light illuminates when power is applied to load.
BM-A301US5-I2
BM-A301US5-I2
Included Hardware
QTY
Hardware
3
M4 Anchors 1" Long
3
M4 Screws 1" Long
2
8 AWG Jumpers for 240V AC
2
10 AWG Jumpers for 120V AC
1
Wire Nut (For Ground Wires)
INSTALLATION
CAUTION: Before wiring or servicing, power to this time switch and the
equipment it controls must be turned off. Turning off the time switch only
will not prevent a shock hazard. Replace cover plate within housing before
supplying power to time switch. If you are not comfortable installing this
device please contact a licensed electrician. Before installing this product read
all instructions carefully.
Removing Knockout
1. Select knockouts to be used. Remove the inner 1/2" knockout by inserting
a flathead screwdriver on the inner most ring and carefully punching the
knockout loose. Remove slug. If the 3/4" knockout is required, remove the
outer ring with pliers after removing the 1/2" knockout. Smooth edges with
a knife if necessary.
Please refer to Quick Start Guide for Examples and More Details.
Mounting of the Time Switch Box
NOTE - Before mounting be sure to remove knockouts for the wires, (see Quick
Start Guide)
1. In order to mount the box you will need the 3 supplied anchors and 3
supplied screws from the hardware list above. (Anchors included are
designed for mounting on sheetrock.)
2. Using the box as a template, mark with a pencil where the three pilot holes
will be drilled.
3. Using the appropriate drill bit size, drill the pilot holes (Note that if drilling
into wood or metal a specialized drill bit may be needed.)
See Drill Diagram.
Drill Diagram
Material
Drill Bit Size
Anchors Needed?
Soft Wood
5/64"
No
Hard Wood
3/32"
No
Metal
5/64"
No
Sheetrock
3/16"
Yes
4. For sheetrock; use a hammer to gently tap the anchors into the pilot holes.
5. Place the box up to the pilot holes or anchors and insert the screws
accordingly.
Wiring the Device to the Timer
NOTE - For outdoor installation use rain tight or wet location conduit hubs that
comply with requirements of UL 514B (standard for fittings for conduit and
outlet boxes).
1. Remove 2 screws retaining the interior cover panel and remove the panel.
2. Refer to Figure 1 and wiring diagrams to determine appropriate placement
of wires. It is the responsibility of the installer to ensure that all applicable
National and Local code requirements are met. If you are unsure of these
requirements, contact a licensed electrician immediately.
3. GROUNDING: This enclosure is of plastic construction and does not require
a ground connection. This enclosure does not provide grounding between

Advertisement

loading

Summary of Contents for GE GE 15136

  • Page 1 GE 15136 Timer APPLICATION Included Hardware This digital GE Time Switch (15132) is a universal, electromechanical time Hardware switch which can be field configured for various power supply voltages. The voltage options include 120VAC, 208/240VAC and 277VAC – all within M4 Anchors 1”...
  • Page 2 PRESSURE PLATE WARNING: Failure to properly configure the dipswitch will result in damage to the unit and void any warranty! Before installing and wiring the GE Time Switch, proper configuration must Typical Wiring Diagrams—SPDT Typical Wiring Diagrams—DPDT be selected. Unit is shipped with DIP Switches set for 277VAC...
  • Page 3 Advanced Settings Programming Countdown Operation: Summer Time Feature (DST): 1. Press the “Timer” button to scroll through the 9 events settings to get to Press the “H+” and “M+” buttons for 3 seconds to advance the current time the ON C setting. 1 hour, SUMMER should appear on the display.