Bay control REC650 ANSI
Product version: 1.2
state part is toggled. The function also
propagates timestamp and quality of input signals.
• INDEXTSPQT extracts individual signals from a
group signal input. Value part of single position
input is copied to SI_OUT output. Time part of
single position input is copied to TIME output.
State bits in common part and indication part of
inputs signal is copied to the corresponding state
output. The function also propagates timestamp
and quality of input signal.
Boolean 16 to Integer conversion B16I
Boolean 16 to integer conversion function (B16I) is
used to transform a set of 16 binary (logical) signals
into an integer.
Boolean 16 to Integer conversion with logic node
representation B16IFCVI
Boolean 16 to integer conversion with logic node
representation function (B16IFCVI) is used to
transform a set of 16 binary (logical) signals into an
integer.
Integer to Boolean 16 conversion IB16A
Integer to boolean 16 conversion function (IB16A) is
used to transform an integer into a set of 16 binary
(logical) signals.
Integer to Boolean 16 conversion with logic node
representation IB16FCVB
Integer to boolean conversion with logic node
representation function (IB16FCVB) is used to
transform an integer to 16 binary (logic) signals.
IB16FCVB function can receive remote values over
IEC61850 depending on the operator position input
(PSTO).

10. Monitoring

IEC61850 generic communication I/O function
SPGGIO
IEC61850 generic communication I/O functions
(SPGGIO) is used to send one single logical signal
to other systems or equipment in the substation.
IEC61850 generic communication 1/O function 16
inputs
IEC 61850 generic communication I/O functions 16
inputs (SP16GGIO) function is used to send up to
16 logical signals to other systems or equipment in
the substation.
Measurements CVMMXN, CMMXU, VNMMXU,
VMMXU, CMSQI, VMSQI
The measurement functions are used to get on-line
information from the IED. These service values
make it possible to display on-line information on
the local HMI and on the Substation automation
system about:
• measured voltages, currents, frequency,
active, reactive and apparent power and power
factor
• primary and secondary phasors
• current sequence components
• voltage sequence components
Event counter CNTGGIO
Event counter (CNTGGIO) has six counters which
are used for storing the number of times each
counter input has been activated.
Disturbance report DRPRDRE
Complete and reliable information about
disturbances in the primary and/or in the secondary
system together with continuous event-logging is
accomplished by the disturbance report
functionality.
Disturbance report DRPRDRE, always included in
the IED, acquires sampled data of all selected
analog input and binary signals connected to the
function block with a, maximum of 40 analog and
96 binary signals.
The Disturbance report functionality is a common
name for several functions:
• Sequential of events
• Indications
• Event recorder
• Trip value recorder
• Disturbance recorder
1MRK 511 265-BUS B