Abnormal Phenomena - Haier WS49GDB Service Manual

Hide thumbs Also See for WS49GDB:
Table of Contents

Advertisement

SERVICE MANUAL
Model: WS49GDB

8-1. Abnormal phenomena

Problems
Reasons
1. Fuse is broken
2. The contact of plug, socket, and cable is not
good. Cable broken.
3. The voltage is too low, 10-15% less than rated
voltage
4. The knob of temperature controller is at "rest"
Compressor
position.
can
not
be
5. The temperature controller is out of order.
started
6. Starting relay or thermal protection unit is out
of order or broken.
7. Wire broken of motor starting coil or operation
coil.
8. The compressor motor is burned or rotator
and stator are blocked to dead.
9. There is leakage of high-pressure gas valve or
the shaft is embraced to dead.
Compressor
1. The point of sensor was moved.
starts
too
2. The temperature controller is out of order.
frequent,
3. The environment temperature is too high,
operation time
humidity too high, airflow is impeded.
too long, but
4. The frost layer at the evaporator is too thick.
temperature
5. The refrigerant is insufficient or leakage.
drop in wine
6. Compressor efficiency is reduced.
cellar
is
too
7. The drying filter is blocked.
slow
Compressor
runs
without
1. The point of sensor was moved.
stop,
2.The temperature sensing probe of controller is
temperature in
not placed well, and causes maladjustment
freezer is too
3. Compressor efficiency reduced.
low
Issue 2014-12-10
Rev.
FZ1412S025V3
Removing methods
1. Check if there is short circuit and
solve it, if not, change capable fuse
2. Check and connect tightly, or
change.
3. Use till voltage rises to rated value
or attach a stabilizer.
4. Rotate the knob to wanted position
for suitable temperature.
5. Change the controller.
6. Change starting relay or thermal
protection unit.
7. Measure using R×1 position of
avometer, if there is wire broken,
change compressor.
8. Change compressor.
9. Change compressor.
1 Check the point of sensor, and move
it to original place.
2. Change the temperature controller.
3. Put the wine cellar to suitable place
and make air circulate well.
4Remove frost regularly.
5. Check or supplement refrigerant.
6. Change compressor.
7. Change new drying filter.
1. Check the point of sensor, and
move it to original place.
2. Adjust to suitable position, normally
contact tightly with evaporator cover.
3. Change compressor.
23