2.1 General specifications
The general specifications are equivalent to the PLC main unit.
→ For general specifications, refer to the manual of the PLC main unit.
2.2 Installation
The product is mounted by the following method.
• DIN rail mounting
• Direct mounting (mounting screw: M4 screw)
For details, refer to the respective PLC manual.
3. Power supply/output specifications and examples of
external wiring
WIRING
PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before
attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
WIRING
PRECAUTIONS
• When drilling screw holes or wiring, make sure cutting or wire debris does not
enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• Make sure to properly wire to the terminal blocks in accordance with the
following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit,
wire breakage, malfunctions, or damage to the product.
- The disposal size of the cable end should follow the dimensions described
in the manual
- Tightening torque should follow the specifications in the manual
- Tighten the screws using a Phillips-head screwdriver No.2 (shaft diameter
6 mm (0.24") or less). Make sure that the screwdriver does not touch the
partition part of the terminal block.
STARTUP AND
MAINTENANCE
PRECAUTIONS
• Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
* For repair, contact your local Mitsubishi Electric representative.
• Do not drop the product or exert strong impact to it.
Doing so may cause damage.
• Do not use the chemicals for cleaning.
• If there is the possibility of touching the PLC inside a control panel in
maintenance, make sure to discharge to avoid the influence of static
electricity.
DISPOSAL
PRECAUTIONS
• Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
TRANSPORTATION AND
STORAGE PRECAUTIONS
• The product is a precision instrument. During transportation, avoid impacts
larger than those specified in the general specifications by using dedicated
packaging boxes and shock-absorbing palettes.
Failure to do so may cause failures in the product.
After transportation, verify operation of the product and check for damage of
the mounting part, etc.
3.1 Wiring
3.1.1
Cable end treatment and tightening torque
For the terminals of FX
-8EYR-S-ES/UL, M3 screws are used.
2N
The electric wire ends should be treated as shown below.
Tighten the screws to a torque of 0.5 to 0.8 N
m
Do not tighten terminal screws with a torque outside the above-mentioned range.
Failure to do so may cause equipment failures or malfunctions.
• When one wire is connected to one terminal
3.2 (0.13")
Terminal
Solderless
screw
terminal
6.2 mm (0.24")
or less
3.2 (0.13")
6.2 mm (0.24")
Terminal
or less
<Reference>
Terminal
Applicable
Type No.
Certification
cable
manufacturer
bonding tool
FV1.25-B3A
AWG22 to 16
J.S.T. Mfg.
YA-1 (J.S.T. Mfg.
UL Listed
Co., Ltd.
Co., Ltd.)
FV2-MS3
AWG16 to 14
• When two wires are connected to one terminal
*1
3.2 (0.13")
Terminal
Solderless
6.2 mm (0.24")
screw
terminal
or less
6.3 mm(0.25")
or more
3.2 (0.13")
6.2 mm (0.24")
Terminal
or less
6.3 mm(0.25")
or more
<Reference>
Terminal
Applicable
Type No.
Certification
cable
manufacturer
bonding tool
J.S.T. Mfg.
YA-1 (J.S.T. Mfg.
FV1.25-B3A
AWG22 to 16
UL Listed
Co., Ltd.
Co., Ltd.)
*1 To adapt the LVD directive (EN61010-2-201:2013) of the EC directive, avoid the
wiring with two wires to the built-in terminal, and take an appropriate action such
as adding an external terminal.
For the time of compliance with the LVD directive (EN61010-2-201:2013), refer
to the manual of the PLC to be connected.
3.2 Power supply specifications
Item
Specifications
24V DC 75mA
24V DC power is either supplied internally from the main unit or
*1
Internal 24V DC
input/output extension unit, or from an extension power supply
unit.
5V DC 30mA
5V DC power is either supplied internally from the main unit or
*1
5V DC
input/output extension unit, or from an extension power supply
unit.
*1 For details on power supply connections, refer to the respective PLC manual.
Power supply specification is the same as the FX
2N
-8EYR(-ES/UL). When there
is not a description in the PLC manual, please select in the same way as the
FX
-8EYR(-ES/UL).
2N
3.3 Output specifications and example of external wiring
3.3.1
Relay output specifications
Item
8 points (A ll points have separate referenc e
Number of output points
terminals (Commons))
Output connecting type
Terminal block
Output form
Relay
30V DC or less, 240V AC or less
External power supply
(Between 250V and 240V CE, UL, and cUL are not
compliant.)
Resistance
2A/1point
load
Max. load
Inductive
80VA/1point
load
Pressure
Min. load
5V DC, 2mA (reference value)
Open circuit leakage current
OFF→ON
Response
Approx. 10ms
time
ON→OFF
Circuit insulation
Mechanical insulation
Display of output operation
LED lights when power is applied to relay coil.
3.3.2
Example of relay output wiring
FX
-8EYR-S-ES/UL
2N
Load
Y0
Fuse
Pressure
Y0
24V DC
Load
Y7
Fuse
Y7
100V AC
4. Terminal layouts
「电器电子产品有害物质限制使用标识要求」的表示方式
Output specifications
Note: This symbol mark is for China only.
含有有害6物质的名称, 含有量, 含有部品
本产品中所含有的有害6 物质的名称, 含有量, 含有部品如下表所示。
 
产品中有害物质的名称及含量
部件名称
外壳
可编程
-
控制器
印刷基板
本表格依据SJ/T 11364的规定编制。
○:表示该有害物质在该部件所有均质材料中的含量均在GB/T 26572
规定的限量要求以下。
×:表示该有害物质至少在该部件的某一均质材料中的含量超出GB/T
26572规定的限量要求。
This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Warranty
Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:
(1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
(2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.
(3) Special damages and secondary damages whether foreseeable or not, compensation for
accidents, and compensation for damages to products other than Mitsubishi products.
(4) Replacement by the user, maintenance of on-site equipment, start-up test run
and other tasks.
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
This product has been manufactured under strict quality control. However
when installing the product where major accidents or losses could occur if the
product fails, install appropriate backup or failsafe functions in the system.