VAMP 121 User Manual

Arc protection unit
Hide thumbs Also See for 121:

Advertisement

Quick Links

VAMP 121
Arc protection unit
User manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 121 and is the answer not in the manual?

Questions and answers

Robert Kinnaird
April 23, 2025

IS THERE A 3D CAD MODEL OF THE VAMP 121?

User image 6808e091049e8

Summary of Contents for VAMP 121

  • Page 1 VAMP 121 Arc protection unit User manual...
  • Page 2 VAMP 121 Arc protection unit VAMP Ltd User manual VAMP 24h support phone : +358 (0)20 753 3264 VM121.EN01...
  • Page 3: Table Of Contents

    9.2. External supply unit / Alarm relay ........17 9.3. VA 1 DA arc sensor ............18 9.4. Mounting plates for VA 1 DA.......... 18 10. Order information..............19 11. Reference information ............20 VM121.EN011 VAMP 24h support phone : +358 (0)20 753 3264...
  • Page 4: General

    Figure 1.1-1. Arc protection unit VAMP 121 1.2. Unit features VAMP 121 is a state of the art arc protection unit for electrical power distribution systems. By using VAMP 121 in switchgears considerable safety improvements are obtained in the form of minimized injury and damage in case of an arc fault.
  • Page 5: Unit Configuration

    System Fault alarm is activated. The same function is attained by activating the binary input on connector X2-7, X2-8 (see also inputs). When the blocking function is activated, the error led is lit and the SF-relay activated. VM121.EN011 VAMP 24h support phone : +358 (0)20 753 3264...
  • Page 6 SW7 on, SW6 off  Trip alarm (active when tripping) SW7 off, SW6 on  Combined internal fault and trip alarm (active either at internal fault or at tripping). Figure 2-2. Alarm relay function table. VAMP 24h support phone : +358 (0)20 753 3264 VM121.EN01...
  • Page 7: Sensors

    The active part of the sensor is mounted in a 10 mm hole, to the area in the switchgear that should be protected, and fastened with a 4 mm self-tapping screw (see Figure 3.1-3). VM121.EN011 VAMP 24h support phone : +358 (0)20 753 3264...
  • Page 8: Portable Arc Sensor Va 1 Dp

    (VA1 DA). VA 1 DP Figure 3.2-1. Portable arc sensor VA 1 DP NOTE! To avoid false activations, the portable sensor must be disconnected from the unit immediately after use. VAMP 24h support phone : +358 (0)20 753 3264 VM121.EN01...
  • Page 9: Functions

    Arc protection unit VAMP 121 User manual Functions VAMP 121 includes an extensive self-supervision. The self- supervision includes internal functions as well as all arc sensors. Figure 4-1. Self-supervision block diagram When an internal fault occurs the self-supervision relay is activated and the ERROR-led is lit.
  • Page 10: Change Of Dip-Switch In Vamp 121

    VAMP Ltd User manual Change of DIP-switch in VAMP In VAMP 121 unit delivered before 11 March 2005, the DIP- switch is in an order opposite to the order shown in the photos in this manual. Units delivered before this date can be identified from the following external details.
  • Page 11: Switchgear Application

    User manual Switchgear application Every compartment is equipped with an arc sensor. Up to ten sensors can be connected to the VAMP 121 unit. The trip relay is electromechanical and can be connected directly to control the circuit-breaker (see specifications).
  • Page 12: Connections

    Figure 7-1. VAMP 121 system components 7.1. Outputs The VAMP 121 unit has an integrated relay output (X2-15,X2- 16) for tripping of the circuit-breaker. Furthermore, one binary output is available (+24V dc) X2-9 (-) X2-10(+), which becomes inactive (0V) on internal fault (SF) and / or on tripping (configurable).
  • Page 13: Inputs

    VAMP 121 User manual 7.2. Inputs VAMP 121 has 10 arc sensor inputs X1:1-20, and one connection for a portable arc sensor (VA 1 DP). All these inputs have continuous self-supervision. Furthermore, one binary input is available for blocking of the output relay e.g.
  • Page 14: Auxiliary Voltage

    90...250V dc. The output (+24V dc) on the voltage module MINI-PS is connected directly to the terminals X2-1 (+) and X2- 2 (-) on VAMP 121. If the auxiliary voltage in the switchgear is 24V dc it can be directly connected to the terminals X2-1 (+) and X2-2 (-) on VAMP 121.
  • Page 15: Technical Data

    - RF electromagnetic field test (According. to f = 80….1000 MHz 10V /m EN 61000-4-3, class III) - Conducted RF field (According. to EN 61000- f = 150 kHz….80 MHz 10V 4-6, class III) VM121.EN011 VAMP 24h support phone : +358 (0)20 753 3264...
  • Page 16: Voltage Tests

    -35…+70°C Transport and storage temp. range -40…+70°C External supply unit (MINI PS) 120...230V ac, 90...250V dc 24V dc Alarm relay (DEK-REL-G24/21) Control 24V dc from VAMP121 Rated voltage 250V ac/dc VAMP 24h support phone : +358 (0)20 753 3264 VM121.EN01...
  • Page 17: Dimensions

    Arc protection unit VAMP 121 User manual Dimensions 9.1. VAMP 121 Figure 9.1-1. Arc protection unit VAMP 121 dimensions 9.2. External supply unit / Alarm relay OUT 24Vdc IN 110-140 V nc nc Figure 9.2-1. External supply unit and alarm relay dimensions VM121.EN011...
  • Page 18: Va 1 Da Arc Sensor

    VA 1 DA arc sensor Figure 9.3-1. VA 1 DA arc sensor dimensions 9.4. Mounting plates for VA 1 DA VYX 001 VYX002 10 mm 10 mm 3 mm Figure 9.4-1. Mounting plate dimensions. VAMP 24h support phone : +358 (0)20 753 3264 VM121.EN01...
  • Page 19: Order Information

    VAMP 121 Supply unit MINI_PS 28 66 446 Alarm relay DEK_REL_ 29 64 500 Arc sensor, 6 m cable VA 1 DA-6 Arc sensor, 20 m cable VA 1 DA-20 VM121.EN011 VAMP 24h support phone : +358 (0)20 753 3264...
  • Page 20: Reference Information