Fresh air ventilation is optional.
Fresh air may be brought into the structure by connecting an insulated duct from outside the structure to
the 6" inlet of the Ultra-Aire SD12. A ventilation control is needed to program the time and frequency that
the unit introduces outside air. The time and frequency of ventilation should be based on the size and
occupancy of the residence.
• The fresh air ventilation duct should be connected to the 6" round collar on the front of the Ultra-Aire
SD12.
• An insulated 6" diameter duct provides up to 100-150 CFM of outside air.
• If a motorized damper is not being used, fresh air is controlled by the manual damper in the 6" collar
of the Ultra-Aire SD12. Performance of the Ultra-Aire SD12 can be impacted by inside and outside air
conditions.
• When a 6" motorized damper is used, a digital control is required.
• It may be necessary to use 8" duct work if additional fresh air is required.
• In cold climates or at times when the dew point is low, ventilation can be used to dehumidify the
structure, making the Ultra-Aire SD12 capable of year-round drying.
Fresh Air Ventilation With Dehumidifier Off and Fan Only Operation
Outside air mixes with the dehumidifier's return air before being supplied to the home. Outside
temperature, inside temperature and relative humidity will impact the combined outlet air conditions.
6" Fresh Air Inlet
A
(Optional)
10" Return Air Inlet
B
10" Supply Air Outlet
C
6" Fresh Air Inlet
A
(Optional)
10" Return Air Inlet
B
10" Supply Air Outlet
C
Note: Temperature and relative humidity may vary depending on duct distribution scheme.
www.Ultra-Aire.com | (800) 533-7533

FRESH AIR VENTILATION

A
Outdoor Air
90°F, 65%RH
B
Indoor Air
70°F, 50%RH
C
Outlet Air
75°F, 65%RH
A
Outdoor Air
30°F, 65%RH
B
Indoor Air
70°F, 50%RH
C
Outlet Air
59°F, 51%RH
Hot Climate
Mixed Air
Mixed Air
75°F
75°F
65%RH
65%RH
Cold Climate
Mixed Air
Mixed Air
59°F
59°F
51%RH
51%RH
Ultra-Aire SD12 Installation Instructions
25