4.

Handling

Before carrying out any operation, always check that the
operating mechanism springs are discharged and that the
apparatus is in the open position.
Circuit-breakers up to 24 kV
– To lift and handle the circuit-breaker, use the tool (1) (fig. 2a:
shortest hooks for circuit-breakers up to 17.5 kV; all hooks
for 24 kV circuit-breakers).
– Put the hooks (2) in the holes prepared in the circuit-breaker
frame and lift.
– On completion of the operation (and in any case before
putting into service) unhook the lifting tool (1) (fig. 2b) and
dismantle the crosspiece (2) by unscrewing the screws (3).
1
Fig. 2a
Fig. 2b
8
36 kV circuit-breakers
– Attach the tools (1) to lift and handle the circuit-breaker
(fig. 2c);
– Attach the hooks (2) as illustrated in fig. 2d and lift;
– On completion of the operation, remove the tools (1).
Always take great care during handling not to stress the
insulating parts and the circuit-breaker terminals.
The apparatus must not be handled by inserting
lifting devices directly under the apparatus itself.
Should it be necessary to use this method, place
the circuit-breaker on a sturdy supporting surface
(see fig. 3).