Section 4
Setting up a project
28
Administrator rights are required to change the PC communication
setup. Some PCs have the feature to automatically detect that Tx
signals from the IED are received on the Tx pin on the PC. Thus, a
straight (standard) Ethernet cable can be used.
When a PC is connected to the IED and the setting DHCPServer is set to On via the
local HMI path Main menu/Configuration/Communication/TCP-IP
configuration/ETHFRNT:1/DHCPServer, the IEDs DHCP server for the front port
assigns an IP address for the PC. The PC must be configured to obtain its IP address
automatically as described in the following procedure.
1.
Select Search programs and files in the Start menu in Windows.
IEC13000057 V1 EN
Figure 9:
Select: Search programs and files
2.
Type View network connections and click on the View network connections
icon.
1MRK 511 284-UEN A
IEC13000057-1-en.vsd
650 series
Engineering manual