Download Print this page

Danfoss VLT MCD 200 Installation Instructions Manual page 3

Finger guards
Hide thumbs Also See for VLT MCD 200:

Advertisement

Installation Instructions
4.2 IP20 Protection for MCD5-0245B ~
MCD5-0961B
MCD 500 (enclosure sizes G3B and G4B) models use rubber
finger guards. Rubber finger guards provide IP20 protection
when used with cable of diameter 22 mm or greater.
Installation
1.
MCD5-0245B ~ MCD5-0396B: Screw the finger guard
plate to the base of the soft starter.
MCD5-0469B ~ MCD5-0961B: Screw the finger guard
bracket to the enclosure of the soft starter.
2.
Fit 1 polycarbonate retaining bracket over each finger
guard.
3.
Feed each power cable through the narrow end of
each finger guard. Connect the cables to the
appropriate terminals on the soft starter.
4.
If the cables do not fit through the finger guards,
shorten the finger guards at the narrow end to make
a bigger opening.
5.
Screw each retaining bracket to the finger guard
plate/bracket.
6.
MCD-50469B ~ MCD5-0961B: Fit the finger guard
cover over the bracket to complete the arrangement.
7.
Repeat steps 1–6 for the other set of terminals.
1
Screws
2
Retaining bracket
3
Finger guards
4
Finger guard plate
Illustration 4.4 Finger Guard Installation for MCD 500 G3B
Enclosure Size
MI17A602
Finger Guards
®
VLT
Soft Starter MCD 200/MCD 500
1
2
3
4
5
Illustration 4.5 Finger Guard Installation for MCD 500 G4B
Enclosure Size
4.3 IP20 Protection for MCD5-360C ~
MCD5-1600C
MCD 500 enclosure sizes G4C and G5C use finger guard
chassis enclosures to isolate live bus bars.
NOTICE
Each kit is only sufficient for protection of either top or
bottom cable terminals. If both top and bottom cable
termination is used, 2 finger guard kits are required.
Installation
1.
2.
3.
4.
5.
6.
Danfoss A/S © 04/2016 All rights reserved.
Screws
Retaining bracket
Finger guards
Finger guard bracket
Top cover
Fasten the finger guard base chassis to the main
enclosure of the soft starter using the screws
provided.
Drill power cable access holes into the gland plate
using the pilot holes provided. To prevent excessive
heating of the gland plate due to large eddy
currents, cut horizontal slits between the power cable
holes drilled into the gland plate.
Fit the gland plate to the finger guard base chassis
using the screws provided.
Run the power cables through the holes in the gland
plate and connect to the appropriate bus bar
terminals of the soft starter. To prevent fraying of
cables against the gland plate, fit cable bushes or
glands (not supplied) appropriate for the size of
cable used.
Fit the finger guard cover over the finger guard base
chassis to complete the arrangement.
Repeat steps 1–5 for the other set of terminals.
3

Advertisement

loading

This manual is also suitable for:

Vlt soft starter mcd 500