13. AUTO RESTART

When the power was interrupted by a power failure, etc. during operation, the operation contents
at that time are memorized and when power is recovered, operation is automatically resumed with
the memorized operation contents.
(Table 13 : Operation contents memorized when the power is interrupted)
Operation mode
Set temperature
Set air flow
Set air flow direction
Swing
Economy operation
Thermistor detected position
Timer mode
*It is necessary to set on the DIP-SW1-No,6 of the wired remote controller, to enable the memory backup.
Refer to the installation manual of wired remote controller for details.
14. MANUAL AUTO OPERATION (When using the Wireless RC)
If MANUAL AUTO Button is set, the operation is controlled as shown in Table 14.
If the remote control is lost or battery power dissipated, this function will work without the remote control.
(Table 14)
Operation mode
Setting temp.
Fan control mode
Timer mode
Economy

15. COMPRESSOR PREHEATING

When the outdoor heat exchanger temperature is lower than 5°C and the all operation
has been stopped for 30 minutes, power is applied to the compressor and the compressor is heated.
(By heating the compressor, warm air is quickly discharged when operation is started.)
When operation was started, and when the outdoor temperature rises to 7°C or greater, preheating is ended.
Wireless remote
controller
Auto changeover
24°C
Auto
Continuous (No timer setting available)
OFF
Wired remote controller
(Memory Backup : Disable)
OFF Timer
ON Timer
WEEKLY Timer
Temperature
SET BACK Timer
01-15
Wired remote controller
(Memory Backup : Enable)
: Memorize
: Not memorize