INFOSEC P2 SunRise 3000 User Manual page 28

Table of Contents

Advertisement

Available languages

Available languages

Inverter output over-
Er09
current.
Er11
Inverter over-load.
Inverter short-
Er13
circuits.
Er14
Inverter PLL fails.
Inverter output DC
Er29
current over spec.
Inverter over
Er10
temperature.
Heat sink over
Er18
temperature.
Table 2. Grid fault alarm code and alarm Code Description
LCD
Designation
indicate
Utility voltage
AL00
over-voltage.
Utility voltage
AL01
under-voltage.
Utility voltage
AL02
over-frequency.
Utility voltage
AL03
under-
frequency.
INFOSEC UPS SYSTEM - 4, rue de la Rigotière - 44700 Orvault - FRANCE - www.infosec-ups.com
28
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - hotline@infosec.fr – 04 10 AA 68 203 18
Over-current on the AC
side. This fault code is
displayed if the current in
the AC network is larger
than specified.
Overload on the AC side.
This fault code is displayed
if the load in the AC
network is larger than
specified.
Short-circuit on the AC
side.
The phase of Inverter can't
synchronize with the utility.
The DC component of the
electricity fed into the grid
is longer than permissible
range.
The internal temperature is
too high.
The hest sink temperature
is too high.
Description
Utility voltage greater
or smaller than the
permissible value.
Utility frequency
greater or smaller
than the permissible
value.
1. Turn off AC
breaker, then check
the peripheral AC
system configuration
and the grid
conditions.
2. If error code
keeps recurring,
contact your local
distributor for help.
1. Try to reduce the
ambient
temperature.
2. Move the inverter
to cooler place.
3. If error code
keeps recurring,
contact your local
distributor for help.
Repair
1. Wait for 1 minute, if the grid
returns to normal, the inverter
automatically restarts.
2. Check grid connection, such
as wires and connectors.
3. Make sure grid voltage and
frequency meet the proper
specifications.
4. If error code keeps
recurring, contact your local
distributor for help.