Hanyoung HX4 Instruction Manual page 7

Digital temperature controller hx series
Table of Contents

Advertisement

HX communication - instructions about the D register address
D-register
Parameter
Parameter meaning
address
name
0001
NPV
Current present value (PV)
0002
NSV
Current set value (SV)
0004
SSV
Current set value (SV)
OUT1 control output value of standard type, Total
0005
MVOUT
control output value of heating/cooling type.
OUT1 control output value of standard type,
0006
CH1OUT
OUT1 control output value of heating/
cooling type.
OUT2 control output value of heating/
0007
CH2OUT
cooling type.
When ZONE is OFF, currentlly
applied set value (SV) and PID group
number
0001: SV1, PID group 1
0002: SV2, PID group 2
0008
PIDNO
0003: SV3, PID group 3
When ZONE is OFF, currentlly
applied PID group number
0001: PID group 1
0002: PID group 2
0003: PID group 3
Current state of Alarm 1 and Alarm 2:
0000: Alarm 1 OFF, Alarm 2 OFF
0009
ALMSTS
0001: Alarm 1 ON, Alarm 2 OFF
0002: Alarm 1 OFF, Alarm 2 ON
0003: Alarm 1 ON, Alarm 2 ON
When the OUT2 control output is SCR
(4-20mA) in Heating / Cooling type,
0013
OUT2_IND
it shows the temperature controller
"OUT2 indicator" status.
Current measurement value of the
0014
H1CM
heater break alarm output
Current situation of the AD error.
0016
ADESTS
0001: AD conversion error
Current situation of the input error.
0001:Input sensor Burn-out
0017
ERRSTS
0002: RJC error
0004: Input range exceeded
0008: Less than input range
Autotuning (AT) current state
0000: AT type
0018
AT_STS
9999: AT in progress ("AT indicator" in
the temperature controller front display
blinking)
Zone function set (For the zone position
0102
ZONE
setting, set in RP parameter of each PID group
0104
ARW
ARW (Anti-reset windup) setting
0106
DI.SL
External contact input (DI) function
0107
ALPHA
Alpha factor of 2 DOF PID
0108
UP.RT
Ramp-up temperature setting
0109
DN.RT
Ramp-down temperature setting
0110
RTMU
Ramp-time unit setting
0111
UPTM
Ramp-up time setting
0112
DNTM
Ramp-down time setting
0113
RAMPT
Ramp type selection
Manual output function (when selecting
0120
MVMOD
the manual output, the "AT indicator" in the
temperature controller front display is steady)
0121
MANMV Manual output value (Manual MV) set 0 ~ 100 %
0122
CTRM
Control mode selection
0124
HKSL
Hot-key selection
0300
SVNO
Set value (SV) number selection
0301
SV1
Set value 1 (SV) setting
0302
SV2
Set value 2 (SV) setting
0303
SV3
Set value 3 (SV) setting
0305
AT MODE Auto-tuning (AT) type selection
0306
AT
Auto-tuning (AT)
0310
1.P
PID group 1 proportional band
0311
1.I
PID group 1 integral time
0312
1.D
PID group 1 derivative time
0313
1.MR
PID group 1 manual reset
0314
1.PC
PID group 1 cooling proportional band 0.0 ~ 999.9 %
0315
1.IC
PID group 1 cooling integral time
0316
1.DC
PID group 1 cooling derivative time
0317
1.DB
PID group 1 Heating / Cooling dead band -100.0 ~ 50.0 %
0318
1.RP
PID group 1 zone position setting
0320
2.P
PID group 2 proportional band
0321
2.I
PID group 2 integral time
0322
2.D
PID group 2 derivative time
0323
2.MR
PID group 2 manual reset
0324
2.PC
PID group 2 cooling proportional band 0.0 ~ 999.9 %
0325
2.IC
PID group 2 cooling integral time
0326
2.DC
PID group 2 cooling derivative time
0327
2.DB
PID group 2 Heating / Cooling dead band -100.0 ~ 50.0 %
0328
2.RP
PID group 2 zone position setting
0330
3.P
PID group 3 proportional band
0331
3.I
PID group 3 integral time
0332
3.D
PID group 3 derivative time
0333
3.MR
PID group 3 manual reset
Parameter
Parameter setting
division
Read only
*1
Process
Read only
*1
Process
Read only
*1
Process
*2
Read only
Process
*2
Read only
Process
Read only
*2
Process
Read only
Process
Read only
Process
Read only
Process
Read only
Process
Read only
Process
Read only
Process
Read only
Process
0: OFF, 1: ON
Control Group
0: AUTO, 50.0 ~ 200.0 %
*2
Control Group
0: OFF, 1: ON
Control Group
0 ~ 100 %
Control Group
0: OFF / EUS(0~100 %)
*1
Control Group
0: OFF / EUS(0~100 %)
*1
Control Group
0: Hour, 1: Min
Control Group
0.01 ~ 99.59 [hh.mm]
*2
Control Group
0.01 ~ 99.59 [hh.mm]
*2
Control Group
0: A Type, 1: B Type
Control Group
0: AUTO ,
Control Group
1: MANUAL
Control Group
0: Traditional,
Control Group
1:2 2 DOF PID (2DOF)
0: Auto-tuning (AT) function
Control Group
1: Manual output function
1 ~ 3
Set value setting group
EU(0 ~ 100 %)
*1
Set value setting group
EU(0 ~ 100 %)
*1
Set value setting group
EU(0 ~ 100 %)
*1
Set value setting group
0: Standard Automatic Operation
1: Low value (PV) type
Auto-tuning Group
automatic operation
0: OFF, 1 ~ 4
Auto-tuning Group
0.0 ~ 999.9 %
*2
PID Group
0 ~ 6000 sec
PID Group
0 ~ 6000 sec
PID Group
-5.0 ~ 105.0 %
*2
PID Group
*2
PID Group
0 ~ 6000 sec
PID Group
0 ~ 6000 sec
PID Group
*2
PID Group
EU(0 ~ 100 %), (1.RP < 2.RP) *1
PID Group
0.0 ~ 999.9 %
*2
PID Group
0 ~ 6000 sec
PID Group
0 ~ 6000 sec
PID Group
-5.0 ~ 105.0 %
*2
PID Group
*2
PID Group
0 ~ 6000 sec
PID Group
0 ~ 6000 sec
PID Group
*2
PID Group
EU(0 ~ 100 %), (1.RP < 2.RP) *1
PID Group
0.0 ~ 999.9 %
*2
PID Group
0 ~ 6000 sec
PID Group
0 ~ 6000 sec
PID Group
-5.0 ~ 105.0 %
*2
PID Group
D-register
Parameter
Parameter meaning
address
name
0334
3.PC
PID group 3 cooling proportional band 0.0 ~ 999.9 %
0335
3.IC
PID group 3 cooling integral time
0336
3.DC
PID group 3 cooling derivative time
PID group 3 Heating / Cooling dead
0337
3.DB
band
0400
HBA
Heater break alarm (HBA) current set 0: OFF, 1 ~ 50 A
Heater break alarm (HBA) Hysteresis
0401
HDB
(deadband) set.
0410
A1TY
Alarm 1 type setting
0411
A2TY
Alarm 2 type setting
0413
A1DB
Hysteresis (dead band) of alarm 1
0414
A2DB
Hysteresis (dead band) of alarm 2
0416
AL-1
Set value of alarm 1
0417
AL-2
Set value of alarm 2
0500
RET
Retransmission output type selection
0501
RET.H
Retransmission output upper limit setting -1999 ~ 9999
0502
RET.L
Retransmission output lower limit setting -1999 ~ 9999
0503
RET.T
Retransmission output form
0600
OUT
Output type selection
0601
o.ACT
Output operation selection
0602
CT
Cycle type (Control cycle)
0603
CTC
Cooling cycle type (cooling control cycle) 1 ~ 1000 sec
General type. ON/OFF control hysteresis Standard type,EUS(0~100%) *1
0604
HYS
Heating / Cooling type.
ON/OFF control hysteresis
0605
PO
Output1 setting when input breaks
0606
POC
Output2 setting when input breaks
0607
OL-H
Output upper limit function
0608
OL-L
Output lower limit function
0610
INP
Input type selection
0611
UNIT
Temperature unit selection
0612
FR-H
Upper range selection
0613
FR-L
Lower range selection
Decimal point position selection
0614
DP-P
during the voltage input)
Scale upper limit setting
0615
SL-H
(during voltage input)
Scale lower limit setting
0616
SL-L
(during voltage input)
0617
FILT
Measurement value filter selection
0618
BIAS
Measurement value correction setting EUS(-100 ~ 100%)
0619
B.OUT
Operation selection when input breaks 0: OFF, 1: UP, 2: DOWN
0624
HYST
Hysteresis type
*1: Please check the presence or absence of the decimal points according to the
input type and range settings
· Set value with decimal points : if you want to input an SV1 of 100.0℃ through
communication, transmit 03E8(100). (03E8 is the hex value of 1000)
· Set value without decimal points: if you want to input an SV1 of 100℃ through
communication, transmit 0064(100). (0064 is the hex value 100)
*2 : Set value with decimal places.
※ For the instructions of the protocol regarding communication, please refer to the
Hanyoung protocol instruction manual on Hanyoung Nux homepage(www.hynux.com).
How to dismantle case
● HX4
-7-
Parameter setting
*2
0 ~ 6000 sec
0 ~ 6000 sec
-100.0 ~ 50.0 %
*2
0 ~ 50
0: OFF, 1 ~ 21
0: OFF, 1 ~ 21
EUS(0 ~ 100 %)
EUS(0 ~ 100 %)
PV al a rm: EU (-100 ~ 100 %)
*1 Alarm Group
Devi a ti o n al a rm: EUS (-100 ~ 100 %)
0: Indicated value
1: Set value (SV)
2: Control output value (MV)
3: Power SPS for the sensor
0: 4 - 20 mA, 1: 0 - 20 mA
0~12 (refer to the number of
control output type selection)
0: Reverse operation (heating),
1: Direct action (cooling)
1 ~ 1000 sec
Heating / Cooling type
*2
0 ~ 10.0%
-5.0~105.0%
*2 Output group
0~105.0%
*2 Output group
Standard type,
*2
OL-L +1 digit ~ 105.0 %
Heating / Cooling type,
0.0 ~ 105.0 %
Standard type,
*2
-0.5 % ~ OL-H-1 digit
Heating / Cooling type,
0.0 ~ 105.0 %
1~31
0: ℃, 1: ℉
EU(0 ~ 100 %)
*1
EU(0 ~ 100 %)
*1
0: No decimal points
1: 1 decimal place
2: 2 decimal places
3: 3 decimal places
-1999 ~ 9999
-1999 ~ 9999
0: OFF, 1 ~ 120 sec
*1
0: CENTER ,
1: EDGE
● HX2
● HX3
● HX7
● HX9
Parameter
division
PID Group
PID Group
PID Group
PID Group
Heater break
alarm group
Heater break
alarm group
Alarm Group
Alarm Group
Alarm Group
Alarm Group
Alarm Group
Retransmission
group
Retransmission
group
Retransmission
group
Retransmission
group
Output group
Output group
Output group
Output group
Output group
Output group
Output group
Input group
Input group
Input group
Input group
Input group
Input group
Input group
Input group
Input group
Input group
Output group