Specification - Hanyoung HX4 Instruction Manual

Digital temperature controller hx series
Table of Contents

Advertisement

Function 11 : Hysteresis type
According to selection of Hysteresis type in ON/OFF control, ON/OFF turning point is as follows:
ex) HYS.t: Cntr(center)
- Hysteresis type sets center,
• In heating control, OFF point is SV + HYS/2 and ON point is SV - HYS/2.
• In cooling control, OFF point is SV - HYS/2 and ON point is SV + HYS/2.
Temperature (℃)
105
SV : 100
95
100 %
Output signal
0 %
Control direction: rEV(Heating)
Temperature (℃)
15
SV : 10
5
100 %
Output signal
0 %
Control direction: dlr(cooling)
ex) HYS.t: EdGE(edge)
- Hysteresis type sets with edge,
• In heating control, OFF point is SV and ON point is SV - HYS.
• In cooling control, OFF point is SV and ON point is SV + HYS.
Temperature (℃)
SV : 100
90
100 %
Output signal
0 %
Control direction: rEV(Heating)
Temperature (℃)
20
SV : 10
100 %
Output signal
0 %
Control direction: dlr(cooling)
Function 12 : Manual output function
If you want to use manual output function, there are 2 ways as follows.
1. Select ON in manual output(MV.Mo) of control group(G.CtL) and current control output amount
converts manual output value. When choose OFF, manual output converts back to auto-output
control.
2. Select manual output function in hot-key(Hk.SL) of control group(G.CtL) and press
hot-key(SET+UP) for 3 seconds at the front panel for manual control output.
When press hot-key(SET+UP)again, manual output converts back to auto-output control.
Note: When auto-tuning(AT) runs, 'AT indicator' flashes at the front panel.
(When manual output is 'ON', 'AT indicator' lights on steady at the front panel.)
Output amount for manual output is adjusted by UP and DOWN key in monitor MV screen.
Function 13 : Factory reset function
This function is used for parameter values to revert to initial setting values.
1 . Select factory reset function (PArA) in control group (G.CtL).
2 . If "1" is selected, input for password will be prompt.
3 . Entering correct password [1304] will reset parameter values to initial setting values and controller
4. In case of input wrong password for 3 times, display will go back to operation screen.
Function 14 : Quick menu setting
HYS : 10 ℃
This function is for selecting frequently used parameters quickly and easily.
1 . Press SET+DOWN key for 3 sec. it will go to the quick menu setting.
2 . SV1, SV2, AL-1, AL-2 values can be set from quick set menu.
3 . Press SET key for 3 sec. to go back to operation screen.
Time
Function 15 : HOT key
Time
This function is for activating/deactivating most frequently used function on operation screen.
1 . Press SET+UP key for 3 sec. to activate hot-key function.
2 . Press SET+UP key for 3 sec. again to deactivate hot-key function.
One of the following two functions can be assigned as hot-key function from the hot-key
select menu (HKSL) in control group (G.CtL) .
1 . AT (Auto-tuning) : ON / OFF
2 . A-M : Automatic control / Manual control

Specification

HYS : 10 ℃
Time
Time
HYS : 10 ℃
Time
Time
HYS : 10 ℃
Time
Time
-6-
will be restarted (power OFF and ON).
P o w e r
s u p p l y
100 - 240 V AC (±10 %), 50/60 Hz
Power consumption
6 W max, 10 VA max
Type
Refer to input type and range
S ampling cycle 62.5 ㎳
Accuracy
±0.5 % of FS (Refer to input type and range)
Allowable voltage Within ±20 V DC (VDC), within ±10 V DC (TC, RTD)
Input
Reference
junction
±3.5 ℃ (0 ~ 50 ℃)
compensation
accuracy
Operation after
T.C: OFF, UP/DOWN RTD: UP
input break
NO : 5 A 250 V AC, 5 A 30 V DC (resistive load)
Relay
NC : 3 A 250 V AC, 1 A 30 V DC (resistive load)
Control
SSR
ON voltage : 12 V DC min, OFF voltage : 0.1 V DC max
output
(voltage pulse)
Load resistance 600 Ω min
SCR
range : 4 – 20 mA (±5%), accuracy : ±0.2 mA
(current)
Load resistance 600 Ω max
range : 4 – 20 mA (±5%), accuracy : ±0.2 mA
Load resistance 600 Ω max
Retransmission output
range : 0 – 20 mA (±5%), accuracy : ±0.2 mA
Load resistance 600 Ω max
Alarm output
5 A 250 V a.c, 5 A 30 V DC (resistive load)
Contact input
OFF resistance : 10 ㏀ min, ON resistance : 1 ㏀ max
Method
ON/OFF, PID control
Control
Output operation
Reverse operation, Direct operation
Anti-reset windup Auto(A=0), 0.1 ~ 100.0 %
Standard
EIA RS485
Max connection
31 units (but, ADDRESS setting : 1 ~ 99)
unit
Communication
2 wire half duplex
method
Data
asynchronous
transmission
Communication
None
sequence
Communication
Within 1.2 km
Interface
distance
Communication
2400, 4800, 9600, 14400, 19200 BPS (parameter selectable)
Speed
Start bit
1 bit
Data length
7 or 8 bit
Parity bit
NONE, EVEN, ODD
Stop bit
1 or 2 bit
Protocol
PC-LINK, PC-LINK SUM, MODBUS-ASCII, MODBUS-RTU
Response time
Processing time in receiving + (response time x 25 ㎳)
Storage
Non-volatile memory(EEPROM) writing 1,000,000 times
Insulation resistance
20 ㏁ min (primary terminal – secondary terminal)
2,300 V AC, for 1 minute
Dielectric strength
(primary terminal – secondary terminal)
Operating ambient
0 ~ 50 ℃, (without condensation)
temperature
Operating ambient
35 ~ 85 % RH (without condensation)
humidity