Inspection Procedure For Blown Fuse On The Indoor And Outdoor Pcb - Mitsubishi Heavy Industries SRK60ZSX-S Technical Manual

Inverter wall mounted type residential air-conditioners, split system, air to air heat pump type
Hide thumbs Also See for SRK60ZSX-S:
Table of Contents

Advertisement

Operation SW ON
(10) How to make sure of wireless remote control
wireless

(11) Inspection procedure for blown fuse on the indoor and outdoor PCB

(
Faulty part, other than
fan motor
Replace the faulty part and the
fuse. Test-run then the unit for
checking.
Replace the indoor and outdoor PCB and the fan motor. Check then the operation.
Measure in this section
wireless
Is the fuse blown on the indoor and
outdoor PCB?
)
YES
YES
Is there any faulty part (fan motor, etc)?
(See pages 67 to 72.)
YES (Fan motor is faulty.)
Is there any damage on the internal circuit
of fan motor?
Check the resistance value to judge.
(See pages 68 to 72.)
Replace the fuse on the indoor and
outdoor PCB. When the operation is
checked without connecting the fan
motor connector, does the fuse blow?
YES
wireless
wireless
Simplified check method of wireless remote control
It is normal if the signal transmission section of the wireless remote
control emits a whitish light at each transmission on the monitor of
digital camera.
Go to the inspection procedure for electric
NO
equipment of indoor and outdoor units
(See pages 67 to 72.)
NO
Replace the fuse, and check the operation.
NO
Replace the fan motor, and check the operation.
69
-
-
'17 • SRK-T-203
wireless
wireless