External Input And Output; External Input - Fujitsu ASYG07LMCE Design & Technical Manual

Wall mounted type
Hide thumbs Also See for ASYG07LMCE:
Table of Contents

Advertisement

9. External input and output

With using external input and output functions, this product can be operated inter-connectedly
with an external device.
Connector
CNA01
Control input
CNB01
CNB02

9-1. External input

With using external input function, some functions on this product can be controlled from an exter-
nal device.
• "Operation/Stop" mode or "Forced stop" mode can be selected with function setting of indoor
unit.
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 150 m.
• The wire connection should be separate from the power cable line.
¢ Control input (Operation/Stop or Forced stop)
The air conditioner can be remotely operated by means of the following on-site work.
Unit operation is started at the following contents by adding the contact input of a commercial
on/off switch to a connector on the external control PCB and turning it on.
Unit operation
Operation mode
Set temperature
Airflow mode
Air direction (swing)
 Circuit diagram example
Indoor unit
Communication kit
control PCB
 When function setting is "Operation/Stop" mode
Input signal
Indoor unit
Input
Operation status output
Error status output
Initial setting after power is on
Auto changeover
24 °C
AUTO
Standard air direction (swing OFF)
Connected unit
Example: Switch
Connector
1
3
10 m*
Optional parts
Locally purchased
On
Off
Operation
Stop
- 19 -
Output
Starting mode other than initial
Mode at previous operation
Temperature at previous operation
Mode at previous operation
Air direction at previous operation
• Contact capacity: DC 24 V or
more, 10 mA or more.
• *: Make the distance from the PCB
to the connected unit within 10 m.
• Use non-polar relays and switches.
Signal
Remarks
See external input/output
settings for details.