Calculations; Calculating Temperature Rise; Calculating Btuh Heating Capacity; Calculating Airflow Cfm - Rheem RHPL-HM2421JC Installation Instructions Manual

Rhpl premium high efficiency equipped with the comfortcontrol2 system
Table of Contents

Advertisement

30

11.0 CALCULATIONS

11.1 CALCULATING TEMPERATURE RISE

• The formula for calculating air temperature rise for electric resistance heat is:
Temperature Rise °F =
Where: 3.16 = Constant, CFM = Airflow

11.2 CALCULATING BTUH HEATING CAPACITY

• The formula for calculating BTUH heating capacity for electric resistance heat is:
BTUH Heating = Watts x 3.412
Where: 1 kW = 1000 Watts, 3.412 = Btuh/Watt

11.3 CALCULATING AIRFLOW CFM

• The formula for calculating airflow using temperature rise and heating BTUH for units
with electric resistance heat is:
Heating BTUH
CFM =
1.08 x Temp. Rise

11.4 CALCULATING CORRECTION FACTOR

• For correction of electric heat output (kW or BTUH) or temperature rise at voltages
other than rated voltage multiply by the following correction factor:
Correction Factor =
3.16 x Watts
CFM
Applied Voltage
2
Rated Voltage
2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rhpl-hm4824jcRhpl-hm3621jcRhpl-hm6024jc

Table of Contents