Event Codes - ABB SPAU 341 C User Manual

Voltage regulator
Table of Contents

Advertisement

Serial
communication
parameters

Event codes

When the voltage regulating module SPCU
1D50 is connected to a control data communi-
cator over the SPA bus, the module generates
events in the format: time, text and event code,
spontaneously to the control data communica-
tion. The text is defined by the user.
Most of the events can be included in or ex-
cluded from the event reporting by writing an
event mask number (V155...V159) to the mod-
ule. The parameters of the event mask are pre-
sented in the tables below.
The event mask is a binary number given in the
form of a decimal number. The events E1...
E33 are represented by the weighting factors 1,
2, 4...128. The event mask number is obtained
by multiplying the above weighting factors by
either 0 (event report excluded) or by 1 (event
report included). and then adding the products
received. The event mask numbers are calcu-
lated in the same way as the checksums of the
switchgroups.
Code Event
E1
Raise counting started
E2
Raise counting reset
E3
Lower counting started
E4
Lower counting reset
E5
Raise output signal activated
E6
Raise output signal deactivated
E7
Lower output signal activated
E8
Lower output signal deactivated
Default value of event mask V155
E9
Auto' input activated
E10
Auto' input deactivated
E11
Manual' input activated
E12
Manual' input deactivated
E13
Raise' input activated
E14
Raise' input deactivated
E15
Lower' input activated
E16
Lower' input deactivated
Default value of event mask V156
The events E50...E54 cannot be excluded from
the event reporting.
At a maximum eight events can be stored in the
event buffer. If a ninth event message is received,
the code E51 is recorded in the buffer. The
buffer and the code E51 are reset by giving the
parameter WC the value 0.
The event codes E52...E54 are generated by the
control data communicator (e.g. SACO 100M,
SRIO 1000M, etc.).
More information about the SPA bus commu-
nication is given in the manual "SPA Bus Com-
munication Protocol", 34 SPACOM 2EN1.
The event codes of the voltage regulating mod-
ule SPCU 1D50 are:
Weighting
Default
factor
1
0
2
0
4
0
8
0
16
1
32
0
64
1
128
0
80
1
0
2
0
4
0
8
0
16
0
32
0
64
0
128
0
0
19