Measured data
12
The measured data is displayed by the three
rightmost digits of the display. The yellow LED
indicators above the display indicate the value
Indicator
Measured value
U
Phase-to-phase voltage. Measuring range 0...1.28 x U
m
U
, submenu Difference between the phase-to-phase voltage and the rated voltage.
m
Measuring range -51.1...28% x U
I
Phase current on phase one. Measuring range 0...2.50 x I
m
I
, submenu
Phase current on phase two. Measuring range 0...2.50 x I
m
I
, submenu
Phase current on phase three. Measuring range 0...2.50 x I
m
U
Difference (U
d
Measuring range -51.1...60% x U
U
, submenu Phase shift of the network, measured by the voltage regulating module.
d
Positive phase shift when having inductive load and negative phase shift at
capacitive load. - - - means a too low I- or U -measurement, to be able to
define the phaseshift.
being displayed. For further information on how
to move in the menu, see "Menu chart".
n
- U
) between the measured voltage and the control voltage U
m
p
n
n
nt
nt
nt
.