Temperature Controller SU-103SR/SU-105DA-N Manual
Model
Temperature Range
SU-103SR
Temperature(-40.0℃~99.9℃)
SU-105DA-N
Temperature(-40.0℃~99.9℃)
※ Thank you for purchasing Samwon ENG product. The User Manual is
provided for preventing the damage and trouble of product caused by
carelessness and to inform the precise usage. Please keep it in the safe place
and refer to it when you have any doubt during using this product.
1. Function & Name of Parts
uncun
Increase
Main Output
Auxiliary Output
시 창
OUT1
OUT2
up
dn
Decreas
Set Cooler
Set Heater
e
Display
Current Temp / Setting Temp
Main/Auxiliary Output
Main/Auxiliary Output ON/OFF Display
Display
At OUT2 Timer ON, If Display Value is set in time,
OUT2 Timer Time Display
Switch ON (Refer to 8. Factory default dP2 item)
Cooler/ Heater
OUT1 rated control (tyP)setting value display
Setting Display
Setting Button
set
Increase Button
up
Decrease Button
dn
Defrost Button
제상
2. Main Output Set Value Change
▶ Supply power to the controller
Display the current temperature.
▶ Press Set button once. Main output set
Temp value in the right picture flashing
▶To change them, press UP & Down Key.
If you press UP/DN longer than 1 sec
Increased or decrease quickly
※If set temp limit function
Is working, the setting will be made
within the range.
▶ If you press Set once again,
the set temp will be saved.
Even if switched-off, the set value
will not be deleted.
▶The current temp displayed and
Controller starts to control.
▶Main Output use terminal 4~5.
Terminal 6 is used for OFF terminal
Should not be used for Main Output.
※Auxiliary output(alarm/timer) use terminal 7, 8. Refer to 9 alarm output setting
and 10 cycle timer setting.
SAMWON ENG
Output
Relay(OUT1,OUT2)
Relay(OUT1,OUT2)
OUT2 Timer Time
시 창
시 창
TIME
제상
set
Display
Temp , Installer Setting Button
Setting Value increase button
Setting Value decrease button
Defrost
Manual
Button
<Current Temp>
< Terminals on Back
>
OUT1
OUT2
sensor
(Main)
(Auxiliary)
① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ ⑩ ⑪ ⑫
AC
220V
Coil terminal
작동
Devi
기계
ce
SU-103SR / SU-105DA Controller User Manual
3. Functions
▶ Only for Heater/Cooler ON/OFF control.
Variation(dIF) 0.1~25.0℃,0~300sec delay timer, forward/converse
Selection function
▶ For Defrost function, Max 999Minutes digital cycle timer/Manual
(only for SU-105DA)
▶ Lock function for installer / Limit function of Set Value
˚ Limit the range of set temperature by users⇒ Set limit function
˚ Hysteresis, delay time, forward/converse selection⇒Lock function
4. Sensor Connection Method
sensor connection method
▶ Please connect as the right picture
DefrostButton
If you connect with the changed
wired or use different type sensor
'Err' to be displayed.
senor wire extension method
Set Button
▶ it is possible within 100m.
You should use the shield inside
cable, in order to prevent
input noise
Sensor Input compensation
(the current Temp is different)
▶ If sensor cable is too long or
sensor is old, there will be temp
variation.
At that time, use current temp
compensation function (rSt).
▶ At the current temp displayed, press set for 3 seconds.
If dIF displayed, release set. In order to move to rSt (temp
compensation), press set several times.
▶ Input the compensation temp by using up&dn.
If you press set for 3 seconds,
it will be saved and the current temp will be compensated.
For example,
Current Temp
20℃
20℃
5. External & Panel Dimension
Power
35
AC
1
100~
220V
6. Set Value Limit & Lock function
① It is possible that users cannot change the default setting, by using
lock function.
Item
Main
메인
전원
Pow
LoC
er
Default
setting
Item
StH
StL
< Terminals on Back
OUT1
sensor
(Main)
① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ ⑩ ⑪ ⑫
Temp sensor
Terminal
sensor
Thermist
SU-103SR
Thermist
SU-105DA
rSt Temp
+
-5℃
=
+
=
10℃
PANEL CUT OUT
73.2
77
Setting
Description
OFF
Locking off. All function setting possible.
Only locking and setting temp function
ON
possible.
setting
Description
50
Settable high temp value 50
40
Settable low temp value 40
>
Power
OUT2
AC
(Auxiliary)
100~
220V
White
White
white
White
Displayed Temp
15℃
30℃
+0.6
70
0.6
28+
(Unit: mm)
Page 1/4

Advertisement

loading
Need help?

Need help?

Do you have a question about the SU-105DA-N and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Samwon Tech SU-105DA-N

  • Page 1 Temperature Controller SU-103SR/SU-105DA-N Manual 3. Functions Model Output Temperature Range ▶ Only for Heater/Cooler ON/OFF control. SU-103SR Temperature(-40.0℃~99.9℃) Relay(OUT1,OUT2) Variation(dIF) 0.1~25.0℃,0~300sec delay timer, forward/converse SU-105DA-N Temperature(-40.0℃~99.9℃) Relay(OUT1,OUT2) Selection function ※ Thank you for purchasing Samwon ENG product. The User Manual is ▶...
  • Page 2 ▶ If you press set for 3 seconds, the value will be saved. 8. Factory Default After that the changed value will be applied. ※ Setting temp value will be in the range of 50~40℃. At the current temp. press up & set together for 3 seconds 7 Installer setting Until FIL displayed, keep up &...
  • Page 3 ▶If you press set buttons for 3 seconds, the data will be saved. ▶ If you press Set button for 3 seconds, the data are saved. 2) Periodic Timer Operation ② Alarm output temperature setting method ①Auxiliary Output is set as periodic output t1. ▶In order to set the alarm output temperature, press set button for 3 Timer output (OUT2) is OFF during OFF setting time, Timer Output(OUT2) is seconds at the status that the current temperature displayed.
  • Page 4 ⑥In the case of preventing to raising the temperature of refrigerator too much during defrost function operation, set the factory default DOF item at the defrost stop temperature value of appropriately. If the temperature of refrigerator is getting defrost higher than DOF temperature, stop immediately and start the normal refrigeration.