FIGURE 14
DC power supply for the 8-slot and 16-slot chassis
2
DC IN
DC OUT ALM
1
1
Screws holding plastic cover
2. Use a Phillips head screwdriver to remove each of the power lugs.
3. Crimp #8 AWG power supply wire into the power lugs and reconnect the power lugs to the power supply unit.
Refer to
Figure
15.
CAUTION
For the NEBS compliant installation of a PowerConnect B-MLXe Series with AC and DC system use a
ground wire of at least 6 American Wire Gauge (AWG). The ground wire should have an agency-approved
crimped connector (provided with the chassis) attached to one end, with the other end attached to
building ground. The connector must be crimped with the proper tool, allowing it to be connected to both
ground screws on the enclosure. Before crimping the ground wire into the provided ground lug, ensure
the bare copper wire has been cleaned and antioxidant is applied to the bare wire.
FIGURE 15
Crimping the power supply wire in the lug
1
#8 AWG power supply wire
4. Re-attach the cover over the power supply lugs that was removed in
5. Connect the -48V cable to the negative terminal and the 0V cable to the positive terminal on the power supply.
NOTE
DC return must be isolated from the router ground (DC-I) when connecting to the power supply.
This equipment installation must meet NEC/CEC code requirements. Consult local authorities for regulations.
PowerConnect B-MLXe Getting Started Guide
53-1001995-01
2
Screws holding power lugs
1
step