Light Commercial R410A on-off S13-01.01.13en Part 1 General Information ....................Part 2 Indoor Units......................Part 3 Outdoor Units....................... 82 Part 4 Installation ......................106 ※The specifications, designs, and information in this book are subject to change without notice for product improvement. General Information...
Light Commercial R410A on-off S13-01.01.13en Part 1 General Information 1. Model Names of Indoor/Outdoor Units......3 2. External Appearance ............4 2.1 Indoor Units ..............4 2.2 Outdoor Units ..............5 3. Nomenclature ..............6 4. Features ................7 General Information...
High Static Pressure Duct 1.2 Outdoor Units Model of outdoor unit and corresponding indoor unit Universal Outdoor unit Model Compressor Brand Matched indoor units Heat Pump SIB-50BAV GMCC Toshiba SOB-50VA SIB-50TAV SIB-60BAV SIB-60TAV GMCC Toshiba SOB-60VA SIB-60DAV SIB-100BAY SIB-100TAY SANYO...
Light Commercial R410A on-off S13-01.01.13en Features (1) Low operation noise ---Streamline plate ensures quietness ---Creates natural and comfortable environment (2) Efficient cooling ---Equal, fast and wide—range cooling (3) The adoption of the most advanced 3- Dimensional Screw fan ---Reduces the air resistance passing through ---Smoothes the air flow ---Makes air speed distribution to the heat exchange uniform (4) Improvement for easy installation and maintenance...
Light Commercial R410A on-off S13-01.01.13en Air Velocity and Temperature Distributions Airflow velocity Temperature Indoor Units. Four-way Cassette Type (Compact)
Light Commercial R410A on-off S13-01.01.13en Electric Characteristics Power Indoor Units Supply Model Voltage Min. Max. SIB-50BAV 220-240V 198V 254V Remark: MFA: Max. Fuse Amps. (A) Indoor Units. Four-way Cassette Type (Compact)
Light Commercial R410A on-off S13-01.01.13en The Specification of Power Type SIB-50BAV Phase 1-phase Power Frequency and Voltage 220-240V, 50Hz Circuit Breaker/ Fuse (A) 40/25 Indoor Unit Power Wiring (mm 3×2.5 Ground wire(mm Outdoor Unit Power Wiring Indoor/Outdoor Connecting Wiring Strong Electric Signal 5×2.5 Weak Electric Signal (mm 2-core shield wire 2×0.75...
Light Commercial R410A on-off S13-01.01.13en 1. Features (1) Low operation noise —Streamline plate ensures quietness —Creates natural and comfortable environment (2) Efficient cooling - Equal, fast and wide range cooling (3) Excellent performance. The optimal evaporator & sufficient airflow volume guarantees the excellent capacity (4) The adoption of the most advanced 3- Dimensional Screw fan —Reduces the air resistance passing through...
Page 24
Light Commercial R410A on-off S13-01.01.13en (8) Swing angle of louver Add one more swing motor, one motor driving two louvers. Controlling the interspace of each part, minimizing the angle loss. The swing angle of the first louver are 40~42 degrees and the second louver are 37~38 degrees.
Page 25
Light Commercial R410A on-off S13-01.01.13en (14) The connecting pipe and drop height is higher. Max. pipe length up to 50m(refer to ①), and Max. drop height up to 30m(refer to ②). (15) Optimal design, smaller Control Box, Space saving and convenient for wiring, Using fire resistance galvanized steel for E-box material.
Light Commercial R410A on-off S13-01.01.13en 4. Service Space The indoor unit should be installed in a location that meets the following requirements: ● There is enough room for installation and maintenance. ● The ceiling is horizontal, and its structure can endure the weight of the indoor unit. ●...
Light Commercial R410A on-off S13-01.01.13en 7. Air Velocity and Temperature Distributions Airflow velocity Temperature Indoor Units. Four-way Cassette Type...
Light Commercial R410A on-off S13-01.01.13en 10. The Specification of Power Cooling & heating Type 24000 Btu/h 36000-48000 Btu/h 60000 Btu/h Phase 1-phase 3-phase 3-phase Power Frequency and 220-240V, 50Hz 380-415V, 50Hz 380-415V, 50Hz Voltage Circuit Breaker/ Fuse (A) 40/25 25/15 40/25 Indoor Unit Power Wiring (mm 3×2.5...
Light Commercial R410A on-off S13-01.01.13en 1. Features 1.1. New design, more modern and elegant appearance. SIB-50TAV 1.2. Convenient installation --The ceiling type can be easily installed into a corner of the ceiling even if the ceiling is very narrow --It is especially useful when installation of an air conditioner in the center of the ceiling is impossible due to a structure such as one lighting.
Light Commercial R410A on-off S13-01.01.13en 10. The Specification of Power Cooling & Heating Type 18000Btu/h 24000Btu/h 36000-60000Btu/h Phase 1-phase 1-phase 3-phase Power 220-240V, Frequency and Voltage 220-240V, 50Hz 380-415V, 50Hz 50Hz Circuit Breaker/ Fuse (A) 20/16 40/25 40/20 Indoor Unit Power Wiring (mm 3×2.5 3×2.5 5×2.5...
Light Commercial R410A on-off S13-01.01.13en 11. Field Wiring CAUTION A disconnection device having an air gap contact separation in all active conductors should be incorporated in the fixed wiring according to the National Wiring Regulation. When wiring, please choose the corresponding chart, or it may cause damage.The signs of the I±J...
Light Commercial R410A on-off S13-01.01.13en Features (1) In case the ceiling is super-high. --Blowing pressure of Indoor unit can reach 160Pa. The air conditioner delivers cold wind to every indoor corner even the ceiling is super-high. Multi-blowing outlets satisfy the fitment’s needs. Fresh air can be supplied, which improves the Indoor air quality greatly.
Light Commercial R410A on-off S13-01.01.13en Service Space Ensure enough space required for installation and maintenance. Indoor Units. HSP Duct Type...
Light Commercial R410A on-off S13-01.01.13en The Specification of Power MODEL 36-60 Phase 1-phase 3-phase Power Frequency and Voltage 220-240V, 50Hz 380-415V~ 50Hz Circuit Breaker/ Fuse (A) 30/15 40/25 Indoor Unit Power Wiring (mm 3x2.5 5x2.5 Ground Wiring ----- ----- Outdoor Unit Power Wiring 3x2.5 5x2.5 Indoor/Outdoor Connecting...
Light Commercial R410A on-off S13-01.01.13en Service Space (Wall or obstacle) More than 30cm Air inlet More than 60cm More than 30cm Maintain channel Air inlet More than 60cm Air outlet More than 200cm Outdoor Units...
T1 Room temp. sensor T2 Evaporator temp. sens GAS SIDE 4-WAY VALVE 3-WAY VALVE ACCUMULATOR COOLING COMPRESSOR HEATING For SOB-50VA, SOB-60VA,the accumulator is not included. SOB-140YA INDOOR OUTDOOR CHECK VALVE LIQUID SIDE (Heating Model only) 2-WAY VALVE T3 Condenser temp. sensor...
Sound Levels 18000Btu/h-48000Btu/h 60000Btu/h Outdoor Unit Microphone 1.0m Note: H= 0.5 × height of outdoor unit Note: The point A is in the middle of the whole outdoor panel. Model Noise level dB(A) SOB-50VA SOB-60VA SOB-100YA SOB-140YA SOB-200YA Outdoor Units...
Light Commercial R410A on-off S13-01.01.13en Troubleshooting 9.1. Self-diagnosis Indoor unit’s LED indication (1) For Big Four-way cassette Outdoor Units. Troubleshooting...
Page 98
Light Commercial R410A on-off S13-01.01.13en (2) For A5 Duct (3) For AHU indoor unit The LED on indoor PCB Type Contents LED1 LED2 LED3 ERROR Pipe Temp sensor error Quick flash ERROR Wire controller input error Quick flash Quick flash (4)For CONSOLE Outdoor Units.
Page 99
Light Commercial R410A on-off S13-01.01.13en (5)For the other types indoor unit Type Contents LED Flashing Remark Operation lamp flashes at Normal Standing-by 0.5Hz Nothing wrong with the Normal System Off All lamps are off unit when LED indicate Normal System startup Operation lamp on these contents.
Page 100
Light Commercial R410A on-off S13-01.01.13en 9.2. Solving steps for typical malfunction (1) For indoor unit a. Indoor room temperature sensor is abnormal Indoor room temperature sensor is abnormal Whether the resistance of the room temp. sensor is 10K Replace room temp. sensor Replace indoor PCB b.
Page 101
Light Commercial R410A on-off S13-01.01.13en d. Outdoor unit malfunction Outdoor unit malfunction Whether the outdoor unit is power on Check when the power is on Replace the outdoor unit Measure whether the voltage of the communication line’s red and black end board between the indoor and outdoor unit is +5V Check the indoor unit main board CN5 or replace the main control board...
Page 102
Light Commercial R410A on-off S13-01.01.13en f. Full-water malfunction Full-water malfunction Check whether the water-level switch is inserted well Insert the water-level switch well Check whether the water-level switch is broken Replace the water-level switch Replace the water pump Check whether the water pump is normal Check PCB board or replace the main control board Temperature sensor error of water pump Whether the resistance of the temp.
Page 103
Light Commercial R410A on-off S13-01.01.13en (2) For the outdoor unit a. Phase sequence error: Phase sequence error Change the order of two of the wires to power supply. Switch on the unit again. If the problem can not be solved, the outdoor PCB is defective b.
Page 104
Light Commercial R410A on-off S13-01.01.13en d. Protection of pressure or temp. Protection of pressure or temp. Is it k1 or K2 open ? Is temp. protective switch K1 open Is pressure protective switch K2 open Possible reason Possible reason The wires is loose to K1 The wires is loose to K2 Air or other gas in the refrigerant.
Page 105
Light Commercial R410A on-off S13-01.01.13en f. Open-circuit and short-circuit trouble of T4 Is connection to connector of temp. sensor good? Check the resistance of the temp. sensor according to Annex 1 Repair connector Is it the resistance is normal? Replace the sensor Indoor PCB is defective.
Page 106
Light Commercial R410A on-off S13-01.01.13en (℃--K) Appendix Indoor Temp. and Pipe Temp. Sensor Resistance Value Table ℃ ℃ ℃ ℃ K Ohm K Ohm K Ohm K Ohm 115.266 12.6431 2.35774 0.62973 108.146 12.0561 2.27249 0.61148 101.517 11.5000 2.19073 0.59386 96.3423 10.9731 2.11241...
Page 107
Light Commercial R410A on-off S13-01.01.13en Part 4 Installation 1.Precaution on Installation ..........107 2.Vacuum Dry and Leakage Checking ......108 3.Additional Refrigerant Charge........110 4.Water Drainage...............111 5.Insulation Work ..............114 6.Wiring ................116 7.Test Operation ..............117 Installation...
Light Commercial R410A on-off S13-01.01.13en Precaution on Installation 1). Measure the necessary length of the connecting pipe, and make it by the following way. Connect the indoor unit at first, then the outdoor unit. Bend the tubing in proper way. Do not harm them. Specially Notice the pipe length/height/dimension of each capacity.
Light Commercial R410A on-off S13-01.01.13en Vacuum Dry and Leakage Checking 2.1 Vacuum Dry: use vacuum pump to change the moisture (liquid) into steam (gas) in the pipe and discharge it out of the pipe to make the pipe dry. Under one atmospheric pressure, the boiling point of water(steam temperature) is 100 .
Page 110
Light Commercial R410A on-off S13-01.01.13en ②. Special vacuum dry procedure This vacuum dry method is used in the following conditions: There’s moisture when flushing the refrigerant pipe. Rainwater may enter into the pipe. Vacuum dry for the first time ······ 2h pumping ③.
Light Commercial R410A on-off S13-01.01.13en Additional Refrigerant Charge Caution ● Refrigerant cannot be charged until field wiring has been completed. ● Refrigerant may only be charged after performing the leak test and the vacuum pumping. ● When charging a system, care shall be taken that its maximum permissible charge is never exceeded, in view of the danger of liquid hammer.
Light Commercial R410A on-off S13-01.01.13en Water Drainage 4.1 Gradient and Supporting 4.1.1 Keep the drainpipe sloping downwards at a gradient of at least 1/100. Keep the drainpipe as short as possible and eliminate the air bubble. 4.1.2 The horizontal drainpipe should be short. When the pipe is too long, a prop stand must be installed to keep the gradient of 1/100 and prevent bending.
Page 113
Light Commercial R410A on-off S13-01.01.13en For Four-way cassette 4.4 Convergent drainage 4.4.1. The number of indoor units should be as small as possible to prevent the traverse main pipe overlong. 4.4.2. Indoor unit with drain pump and indoor unit without drain pump should be in different drainage system. 4.4.3.
Page 114
Light Commercial R410A on-off S13-01.01.13en ③ Stop the air conditioner running, turn off the power, and put back the cover. Stop the air conditioner. After 3 minutes, check if it has abnormity. If the collocation of drainpipes is illogical, the water will flow back overfull, which will cause the alarm lamp flashes, even overflow from the water receipt plate.
S13-01.01.13en Light Commercial R410A on-off Insulation Work 5.1 Insulation material and thickness 5.1.1. Insulation material Insulation material should adopt the material which is able to endure the pipe’s temperature: no less than 70 in the high-pressure side, no less than 120 in the low-pressure side(For the cooling type machine, no requirements at the low-pressure side.) ...
Page 116
Light Commercial R410A on-off S13-01.01.13en 5.3 Drainage pipe insulation The connection part should be insulated, or else water will be condensing at the non-insulation part. 5.4 Note 5.4.1 The jointing area, expanding area and the flange area should be heat insulated after passing the pressure test 5.4.2 The gas and liquid pipe should be heat insulated individually, the connecting part should be heat insulated individually.
Light Commercial R410A on-off S13-01.01.13en Test Operation (1) The test operation must be carried out after the entire installation has been completed. (2) Please confirm the following points before the test operation. The indoor unit and outdoor unit are installed properly. ...