Prohibited pattern
HR1
1
2
48k
48k
• Capacity sum of indoor units is over 160kBtu/hr.
Pattern
1
Indoor unit
A
Low pressure Gas pipe
Outdoor
High pressure Gas pipe
Unit
Liquid pipe
1) Keep the 40m distance from the first branch to the farthest indoor.
2) Keep the horizontal level between HR units.( for example, the same flour. )
Y branch
Keep the sum of indoor capacity is under 160kBtu/hr
3
4
48k
48k
A
HR1
1
2
12k
24k
Y Branch pipe
Gas pipe
HR
Unit
Liquid pipe
1) under 40m
2) Same horizontal level
Indoor
Indoor
Unit
Unit
Keep the sum of indoor capacity is under 160kBtu/hr
1) under 40m
2) Same horizontal level
Indoor
Indoor
Indoor
Indoor
Unit
Unit
Unit
Unit
Pattern
A
36k
HR2
3
4
5
6
7
24k
12k
48k
48k
48k
Indoor
Unit
Indoor
Indoor
Unit
Unit
Indoor
Indoor
Indoor
Indoor
Unit
Unit
Unit
Unit
HR1
HR2
1
2
3
4
36k
36k
36k
8
12k
It's not allowed
Height
Installation Manual 35