Protective Elements; Measurement Elements - Mitsubishi Electric CBV2-A01D1 Instruction Manual

Voltage protection relay, melpro d series
Table of Contents

Advertisement

2.2 Protective elements

Relay without RS232C I/F
Style
Relay with RS232C I/F
Undervoltage
Setting
*24
Overvoltage
Forced operation
Operation indication

2.3 Measurement elements

Relay without RS232C I/F
Style
Relay with RS232C I/F
VT primary voltage
VT secondary voltage
Real time
Max. record
Fault record
*23
*22
The form of display depends on value range as shown in the tables below:
VT primary setting value determines the minimum number of digits to be displayed on each measurement display.
When a value to be displayed exceeds the max. value of the display range, the max. value will blink.
VT primary setting
0 ~ 999[V]
1.00 ~ 9.99[kV]
10.0 ~ 99.9[kV]
100 ~ 999[kV]
*23
When a communication card is connected, waveform data in the event of system fault can be read.
(See the section 4 "Function").
*24
When the product is shipped from the factory, each setting value is "Lock" (With lock setting element) or "minimum
setting value" (Without lock setting element).
Operation voltage
Operation time
When execute the relay test, enable to use the selected input
UV test
phase only. "UV test" LED turn on during selecting "UV TEST".
Operation voltage
Operation time
Forced operation is available for any trip or signaling contact individually.
Operation indicator LED (red) comes on when the relay operates.
100 ~ 999V (1V step)
1000 ~ 9990V (10V step)
10.0k ~ 99.9kV (0.1kV step)
100k ~300kV (1kV step)
100/√3 -110/√3 -115/√3 -120/√3 -100-110-115-120[V]
(57.7) (63.5) (66.4) (69.3)
Indication value = Relay input value
Conversion
×VT primary setting / VT secondary setting
Range *22
0.00 ~ VT primary setting / VT secondary setting ×165 [V]
Update
Approx. 200 ms
Indication value = Relay input value
Conversion
×VT primary setting / VT secondary setting
Range *22
0.00 ~ VT primary setting / VT secondary setting ×165 [V]
Indication value = Relay input value
Conversion
×VT primary setting / VT secondary setting
Range *22
0.00 ~ VT primary setting / VT secondary setting ×165 [V]
100 ~ 500[V]
501 ~ 10000[V]
□□□[V]
□.□□[kV]
□□.□[kV]
□□□[kV]
354PMB
541PMB
LOCK - 10 ~ 110V (1V step)
INST - 0.1 ~ 10 s (0.1 s step)
– AB phase test – BC phase test – CA phase test
OFF
LOCK – 60 ~ 155V (1V step)
INST - 0.1 ~ 10 s (0.1 s step)
354PMB
541PMB
11 ~ 300[kV]
□.□□[kV]
□.□[kV]
□.□□[kV]
□.□[kV]
□□.□[kV]
□□.□[kV]
□□□[kV]
□□□[kV]
7
355PMB
542PMB
355PMB
542PMB
PCKN-OIL738