Control Configuration - Fenwal SERIES 35-67 Manual

24 vac microprocessor based proven hsi control with combustion blower relay
Table of Contents

Advertisement

CONTROL CONFIGURATION

35 - 67
X X X X
®
Page 8
Series 35-67, 24 VAC Hot Surface Ignition Control
- X X X
400 MAIN STREET, ASHLAND, MA 01721
TEL: (508) 881-2000
FAX: (508) 881-6729
www.fenwalcontrols.com
Printed in U.S.A.
© 2009 Kidde-Fenwal
Description
Trial for Ignition
0 = 2 Seconds
1 = 4 Seconds
3 = 7 Seconds
5 = 10 Seconds
7 = 15 Seconds
Proving Current (Amps)
0 = 0.8
1 = 0.5
3 = 2.1
4 = 2.3
5 = 2.7
6 = 3.1
7 = 3.3
Purge Timing
0 = 0 Prepurge, 0 Interpurge, 0 Postpurge
1 = 15 Prepurge, 15 Interpurge, 0 Postpurge
2 = 30 Prepurge, 30 Interpurge, 0 Postpurge
3 = 0 Prepurge, 15 Interpurge, 0 Postpurge (3 Try Units Only)
4 = 0 Prepurge, 30 Interpurge, 0 Postpurge (3 Try Units Only)
5 = 15 Prepurge, 15 Interpurge, 30 Postpurge (Full Time Power)
6 = 30 Prepurge, 30 Interpurge, 30 Postpurge (Full Time Power)
7 = 0 Prepurge, 15 Interpurge, 15 Postpurge (Full Time Power)
8 = 0 Prepurge, 30 Interpurge, 30 Postpurge (Full Time Power)
Tries For Ignition
0 = Single Try - Local Sense. Recycle On Flame Loss
1 = Single Try - Remote Sense. Recycle On Flame Loss
2 = Single Try - Local Sense. Lockout On Flame Loss
3 = Single Try - Remote Sense. Lockout On Flame Loss
5 = Three Tries - Local Sense. Recycle On Flame Loss
6 = Three Tries - Remote Sense. Recycle On Flame Loss
7 = Three Tries - Local Sense. Lockout On Flame Loss
8 = Three Tries - Remote Sense. Lockout On Flame Loss
Dwell Time
0 = 4 Seconds
1 = 6 Seconds
5 = 20 Seconds
7 = 40 Seconds
Full Time Power, Termination, Lockout Type
0 = No Full Time Power, Q.C. Terminals, Automatic Reset
1 = No Full Time Power, Mate-N-Lock, Automatic Reset
2 = Full Time Power, Q.C. TERMINALS, Automatic Reset
3 = Full Time Power, Mate-N-Lock, Automatic Reset
4 = No Full Time Power, Q.C. Terminals, Non-volatile Lockout
5 = No Full Time Power, Mate-N-Lock, Non-volatile Lockout
6 = Full Time Power, Q.C. Terminals, Non-volatile Lockout
7 = Full Time Power, Mate-N-Lock, Non-volatile Lockout
8 = Aftermarket Kits (Consult Factory for Special Number)
9 = Special OEM Features (Consult Factory for Special Number)
Other Features
0 = No Indicators With No Inducer
1 = No Indicators With Inducer
2 = Indicators With No Inducer
3 = Indicators and Inducer
4 = CE Approved Model
9 = Manual Reset (Standard Includes Indicators and Inducer)
These instructions do not purport to cover all the details or variations in the equipment
described, nor do they provide for every possible contingency to be met in connection with
installation, operation and maintenance. All specifications are subject to change without
notice. Should further information be desired or should particular problems arise which are
not covered sufficiently for the purchaser's purposes, the matter should be referred to
KIDDE-FENWAL, Inc., Ashland, Massachusetts.
TAG
www.fenwalcontrols.com
P/N 35.67.03 01/22/09