Fenwal 35-65 Series Manual

Fenwal 35-65 Series Manual

24 vac microprocessor based hsi control with 120/240 field selectable line voltage capability

Advertisement

SERIES 35-65 & 35-66
24 VAC Microprocessor Based HSI Control
with 120/240 Field Selectable Line Voltage Capability
FEATurES
Safe start and full-time flame sensing
120/240 field selectable line voltage for use
with 120 VAC ignitor option
24/120/240 VAC hot surface ignitor models available
Blower control and airflow switch monitoring option
Diagnostic LED
Multiple trials for ignition
Automatic reset option
Local or remote flame sensing
Flame current test pins
Dual speed blower option for LoNox applications
Fail-safe gas valve control (35-66 only)
CE models available
APPLICATIONS
Pool and spa heaters
Gas furnaces
Water heaters
Any 24 VAC gas burner application under 400K BTU
DESCrIPTION
The Series 35-65 and 35-66 controls are designed to perform many
gas-fired 24 VAC appliance functions in a single control, resulting
in lower system cost. This series monitors the demand for heat,
controls the combustion blower, monitors proper airflow, ignites and
maintains the flame during heating, and provides diagnostic support.
The on-board diagnostics with LED output provide assistance with
troubleshooting and ensures safe and efficient burner operation.
The microprocessor circuit design provides precise, repeatable
timing sequences for ignition and purge times (pre-, inter-, and post-)
as well as multiple tries for ignition. The optional 120/240 VAC field
selectable line voltage capability provides additional field service
efficiency and lower inventory costs.
Agency Certifications
Design certified by CSA International to
CAN C22.2 #199-M89 and ANSI Z21.20
for Automatic Ignition Systems, including
UL1998 software review. FM approval
and CE pending on selected models.
www.fenwalcontrols.com
1-800-FENWAL-1

SPECIFICATIONS

Input power
Voltage
Current
output (ContaCt ratIngs)
gas Valve
Combustion Blower
(Model 35-66 only)
Hot surface element
operatIng teMperature
FlaMe sensItIVIty
types oF gas
IgnItor
enClosure
MoIsture resIstanCe
sIze wItH enClosure
weIgHt
Series 35-65, -66
HSI Control
with 120/240 Field Selectable Line Voltage
35-65,-66.02
Control:
18 to 30 VAC 50/60 Hz
(Class 2 Transformer)
Line:
24, 120 or 240 VAC
(L1 & L2 only)
300 mA max @ 24 VAC with blower and gas
valve relay energized (Control only)
2.0A max @ 24 VAC
3.0 FLA max @ 120 VAC (1/4 hp)
1.5 FLA max @ 240 VAC (1/4 hp)
5.0A max @ 120/240 VAC
-40ºF to +176ºF (-40ºC to +80ºC)
0.7 microamps minimum
Natural, LP, or manufactured
24 VAC, 120 VAC, or 240 VAC
mini-ignitors and silicon carbide ignitors
depending on model
Gray (Noryl N-190)
Conformal coated to operate non-condensing
to 95% R.H. Care must be taken to protect
module from direct exposure to water
See Figures on Page 7
8 oz including cover
®
Page 1

Advertisement

Table of Contents
loading

Summary of Contents for Fenwal 35-65 Series

  • Page 1: Specifications

    95% R.H. Care must be taken to protect module from direct exposure to water See Figures on Page 7 sIze wItH enClosure 8 oz including cover weIgHt www.fenwalcontrols.com 1-800-FENWAL-1 Series 35-65, -66 HSI Control with 120/240 Field Selectable Line Voltage Page 1...
  • Page 2 TFI sequence begins preceded by a new TFI sequence after one hour. any pre-purge period. If not, the control will enter a lockout condition with the combustion blower off. www.fenwalcontrols.com 1-800-FENWAL-1 Page 2 Series 35-65, -66 HSI Control with 120/240 Field Selectable Line Voltage...
  • Page 3: Mounting And Wiring

    Operation outside specifications could result in failure of the energize the combustion blower. Should the gas valve later close Fenwal product and other equipment with injury or death to people and damage to property. Service to this product should only be completely and the flame signal be removed, the combustion performed by a qualified technician.
  • Page 4 ("XX") with the length in inches ("l" dimension). Standard wire lengths are 12, 18, 24 30, 36 and 48 inches. Example 05-129845-018 = 18 inches. For other lengths, please contact Fenwal...
  • Page 5 WIrINg DIAgrAmS - SErIES 35-65 loCal FlaMe sensIng (sensIng tHrougH Hot surFaCe IgnItor) 35-65 reMote FlaMe sensIng (sensIng tHrougH Independent FlaMe rod) 35-65 www.fenwalcontrols.com 1-800-FENWAL-1 eries 35-65, -66 HSI Control with 120/240 Field Selectable Line Voltage Page 5...
  • Page 6 WIrINg DIAgrAmS - SErIES 35-66 loCal FlaMe sensIng (sensIng tHrougH Hot surFaCe IgnItor) 35-66 reMote FlaMe sensIng (sensIng tHrougH Independent FlaMe rod) 35-66 www.fenwalcontrols.com 1-800-FENWAL-1 Page 6 Series 35-65, -66 HSI Control with 120/240 Field Selectable Line Voltage...
  • Page 7 DImENSIONS - SErIES 35-65, 35-66 Front and sIde VIews www.fenwalcontrols.com 1-800-FENWAL-1 Series 35-65, -66 HSI Control with 120/240 Field Selectable Line Voltage Page 7...
  • Page 8: Control Configuration

    All specifications are subject to change without notice. www.fenwalcontrols.com Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to KIDDE-FENWAL, Inc., Ashland, Massachusetts. © 2003 Kidde-Fenwal Printed in U.S.A.

This manual is also suitable for:

35-66 series

Table of Contents