TROUBLESHOOTING
10.4.5
The following explains the procedures to be taken when a station has a station No. that is
larger than the total number of stations in a network.
The total number of stations in a network is limited to four.
(1) When GX Developer connected station is normally operating
Control
station
Normal station
Selected
No.1
station
No.2
Normal station
Normal station
No.8
No.3
Control station
Normal station
No.1
No.2
Normal
Normal station
Selected
station
station
No.3
No.8
Figure 10.35 When GX Developer connected station is normally operating
10.4 Checking the Error Description with the CC IE Control Network Diagnostics
Own station No. is out of range
Select the own station.
An error has occurred in station No.8.
Select station No.8.
Click the [Error details] button.
The Error factor indicates that station No.8 is larger than
the total station No. per network.
Take corrective actions according to the troubleshooting.