System Control Esm 37-Esm 50 (Fig. 3 B) - Gardner Denver ESM 30 Original User Manual

Screw air compressor
Table of Contents

Advertisement

4. Design and functioning
Automatic operation (open-close operation)
When the pressure reaches the upper switching
point set on the network pressure sensor (-28 -
(B1)), solenoid valve (- 30 - (Y1)) is deenergised.
The pressure valve (-2.2-) closes because the lower
control space of the adjusting cylinder (-2.1.-) is
relieved by the deenergised valve (-30-(Y1)) the
upper control space is impinged with pressure via
the valve (-32-).
The oil separator tank is relieved to no-load
pressure (residual pressure) via the two valves (-31-
and -32-).
The screw compressor is now running in the offload
mode.
The cooling air ventilator (- 26 -) is switched on or
off in dependence upon the final compression
temperature.
When the pressure at the network pressure sensor
(- 28 - (B1)) does not fall to the set lower switching
point within the set motor run-on time (e.g. 120
seconds), the drive motor (- 3 -) and the cooling air
ventilator motor (- 26 -) are shut down and the
system is depressurised to atmospheric pressure.
The system is now in the "stand-by" mode and can
restart at any time when the network pressure falls
to the lower switching point (see section "Starting of
the system").
When the pressure at the network pressure sensor
(- 28 - (B1) falls to the preset lower switching point
before the set motor run-on time has elapsed,
solenoid valve (- 30 - (Y1)) is energised again.
The unit now changes over to on-load operation.
24
4.5.2 System control ESM 37-ESM 50
(Fig. 3 b)
(See also operating instructions for the compressor
control GD Pilot MK)
Danger
The lower control area of the operating cylinder
(2.1) is generally pressurised (even when the
system is at a standstill). Before working on the
suction regulator this must be bled by carefully
unscrewing the return valve (2.3).
Standstill of the system
During plant standstill the suction regulator (-2)
should be closed via pressurisation in the lower
control area of the operating cylinder (-2.1-).
Solenoid valves (- 19 - (Y1) and - 20 - (Y4)) are
deenergised.
The oil separator vessel (-6-) is released via the
relief valve (-21-) to atmospheric pressure.
Starting the system
The motor starts up in the Y-mode.
The intake regulator is closed.
The compressor aspires a certain amount of air
through a bypass valve. Pressure builds up in the
reservoir.
The oil supply of the screw compressor takes place
through a drop in pressure between the oil separator
vessel and the injection spot in the screw
compressor.
When switching the drive motor over to Δ-mode,
switch the solenoid valves (-19-(Y1) and 20 (Y4) as
these are supplied with power.
The air circulated in the system streams over the
solenoid valve (-20- (Y4)) in the upper control area
of the operating cylinder (-2.1-). The relief valve
(-21-) is closed.
The lower control area of the operating cylinder
(-2.1-) is blocked and bled by the solenoid valve
(-19- (Y1)) from the oil separator vessel.
The pressure control valve (- 2.2 -) in the intake
regulator (- 2 -) opens.
At a reservoir pressure of approx. 4.5 bar/65 PSI the
pressure holding and check valve (- 15 -) opens.
Compressed air is now delivered into the consumer
network.
The system is now in load running mode.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Esm 50

Table of Contents