Troubleshooting - Ultra-Aire 98H Installation Instructions Manual

Table of Contents

Advertisement

Troubleshooting

CAUTION!
TROUBLESHOOTING SHOULD BE PERFORMED BY A QUALIFIED HVAC TECHNICIAN.
Symptom
Neither fan nor
compressor
running.
Dehumidification
is being called for.
Compressor is
not running.
Dehumidification
is being called for.
Fan is running.
Compressor
cycles on and off.
Dehumidification is
being called for.
24
Ultra-Aire 98H Installation Instructions
SERVICE
Possible Reason
1. Dehumidifier unplugged
or no power to outlet.
2. Humidity control set
too high.
3. Loose connection in
internal or control wiring.
4. Defective compressor
relay.
5. Defective control
transformer.
1. Defective compressor
run capacitor.
2. Loose connection in
compressor circuit.
3. Defective compressor
overload.
4. Defective compressor.
5. Defrost thermostat open.
1. Low ambient
temperature and/or
humidity causing unit
to cycle through
defrost mode.
2. Defective compressor
overload.
3. Defective compressor.
4. Defrost thermostat
defective.
5. Dirty air filter(s) or air
flow restricted.
6. Defective fan or relay.
Troubleshooting Procedure
WARNING!
ELECTRICAL SHOCK HAZARD:
ELECTRICAL POWER MUST BE PRESENT
TO PERFORM SOME TESTS. THESE TESTS
SHOULD BE PERFORMED BY A QUALIFIED
SERVICE PERSON.
Troubleshooting Procedure for Control
Related Issues
This method of diagnosis will test the 3 main
components of the control circuit individually to
indicate any potential problems. This is to be used
when the control will not activate the main unit.
1. Detach field control wiring connections from
the terminals on the main unit.
2. Connect the 24V and FAN terminals
together; only the fan should run. Disconnect
the terminals.
3. Connect the 24V and DEHU terminals
together; fan and compressor should run.
Disconnect the terminals.
4. If this test works, the main unit is working
correctly from a control standpoint.
5. Reconnect field control wiring to the terminals
on the main unit.
6. Remove the control panel cover and detach
the field wiring from the control connections.
7. Connect the 24V and FAN terminals together;
only the fan should run. Disconnect the terminals.
8. Connect the 24V and DEHU terminals together;
fan and compressor should run. Disconnect the
terminals.
9. If this test works, then the field control wiring
is ok.
10. If the problem persists, then the control is
most likely faulty.
www.Ultra-Aire.com | (800) 533-7533

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

4034240

Table of Contents