Errors Reported On Other Tools - Xtralis VESDAnet Product Manual

Interface card
Table of Contents

Advertisement

VESDAnet Interface Card Product Guide
Fault Summary 8 - Field Wiring
Explanation:
Communications fault on
VESDAnet. i.e. The VLF-
VN will report this fault if
any device on VESDAnet
has a wiring fault.
The Network connection
has been set as Open
Ended but a device is
actually connected. The
VLF-VN will report this
fault if any device on
VESDAnet has this
problem.
Another device on
VESDAnet has had fault
7, 10, 29, 65, 66 & 67.

Errors reported on other tools

Configuration Error Message
You may see errors of this type when using the LCD Programmer. These
errors occur when you select a setting that is not supported by the VLF with
VN Card. This error will not occur if the configuration settings follow the
guidelines in the previous sections Configuring VLF and VESDAnet Interface
Card on page 11
When this error occurs for the LCD Programmer, you will see:
In the example shown, 4350357 is the serial number of the device that failed,
and the message after that (relay response) is an example of the type of error
message that could be shown.
18
Action:
1. Use VSC connected to VESDAnet to
determine which device is causing this problem
and the fault number. If the fault is intermittent
then view the event log on any VLP, VLC or VLS
detector on the network to determine which
device has the problem.
2. Once you have determined the specific device
and fault number, see VSC help for how to
resolve the fault.
*** WARNING ***
Setup failed from
4350357: Relay
response
Xtralis VESDA
www.xtralis.com
®