Testing And Certification - GE Multilin MM200 Quick Start Manual

Motor management system low voltage motor protection and control
Hide thumbs Also See for MM200:
Table of Contents

Advertisement

QUICKSTART GUIDE

1.5.6 Testing and certification

1.5.7 Physical specifications
MM200 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE
CERTIFICATION
ISO:.............................................................................Manufactured under an ISO9001 registered program
CE: ..............................................................................Conforms to EN 60255-26 (EN 50263), EN 55022/CISPR22/
cULus:.......................................................................Conforms to UL 508 / UL 1053 and C22.2.14-05 (CSA)
TYPE TESTS (* TEST NOT PERFORMED FOR AC PSU)
Relative Humidity Cyclic: .................................IEC 60068-2-30: 55°C at 95% RH
Hot: ............................................................................IEC 60068-2-2 (Hot Start) 16 hours
Cold: ..........................................................................IEC 60068-2-1 (Cold Start) 16 hours
Dielectric Strength:.............................................IEC 60255-5: 2000 V AC
Insulation Resistance:.......................................IEC 60255-5: >100 MΩ / 500 V DC / 10 s
Impulse Voltage:..................................................IEC 60255-5: 5kV
Sinusoidal Vibration:..........................................IEC 60255-21-1: 2 g
Shock and Bump:................................................IEC 60255-21-2: 5 g / 10 g / 15 g
Seismic*:..................................................................IEC 60255-21-3: 2 g
Damped Oscillatory Burst:..............................IEC 60255-22-1: 1 MHz 2.5 kV / 1 kV
Electrostatic Discharge Immunity - Air
and Direct:.........................................................IEC 60255-22-2: 15 kV / 8 kV
Radiated RF Immunity:.....................................IEC 60255-22-3: 10 V/m
Electrical Fast Transient / Burst
Immunity: ..........................................................IEC 60255-22-4: 4 kV
Surge Immunity: ..................................................IEC 60255-22-5: 2 kV / 1 kV
Conducted RF Immunity:.................................IEC 60255-22-6: 150 kHz to 80 MHz 10 V/m rms
Radiated RF Emission: ......................................IEC 60255-25: Group 1 Class A
Conducted RF Emission: ..................................IEC 60255-25: Group 1 Class A
Ingress of Solid Objects and Water:...........IEC 60529: IP54 (front), IP20 (back)
Power Frequency Magnetic Field
Immunity*: ........................................................IEC 61000-4-8: 100 A/m cont; 1000 A/m 1 to 3 seconds
Pulse Magnetic Field Immunity*:.................IEC 61000-4-9: 1000 A/m
Damped Oscillatory Magnetic Field
Immunity*: ........................................................IEC 61000-4-10: 100 A/m
Voltage Dip; Voltage Interruption:...............IEC 60255-11: 5 msec interruption
Fast Transient SWC*:.........................................IEEE C37.90.1: ±4 kV
Oscillatory Transient SWC*: ...........................IEEE C37.90.1: ±2.5 kV
Radiated / Conducted Emissions: ...............EN55022: Class A
Power frequency immunity test*: ...............IEC 60255-22-7: Class A
DIMENSIONS
Size: ...........................................................................Base: 78 mm (W) × 90 mm (H) × 113 mm (D) [+ terminals
Weight (Base):.......................................................0.5 kg
EN 61000-6-2, EN 60255-27
10mm]
BCP: 75 mm (W) × 75 mm (H) × 31 mm (D)
SPECIFICATIONS