Lenovo x3550 M5 Product Manual page 49

1u two-socket rack server
Hide thumbs Also See for x3550 M5:
Table of Contents

Advertisement

Electrical:
Models with 1500 W AC Platinum power supplies:
200 - 240 (nominal) V ac; 50 Hz or 60 Hz; 8.35 A
Input kilovolt-amperes (kVA) (approximately):
Models with 900 W AC Platinum power supplies:
100 to 127 (nominal) V ac; 50 Hz or 60 Hz; 10.3 A
200 to 240 (nominal) V ac; 50 Hz or 60 Hz; 5.0 A
Input kilovolt-amperes (kVA) (approximately):
Models with 750 W Platinum AC power supplies:
100 to 127 (nominal) V ac; 50 Hz or 60 Hz; 8.6 A
200 to 240 (nominal) V ac; 50 Hz or 60 Hz; 4.2 A
Input kilovolt-amperes (kVA) (approximately):
Models with 750 W Titanium AC power supplies:
200 to 240 (nominal) V ac; 50 Hz or 60 Hz; 4.2 A
Input kilovolt-amperes (kVA) (approximately):
Models with 550 W AC power supplies:
100 to 127 (nominal) V ac; 50 Hz or 60 Hz; 6.5 A
200 to 240 (nominal) V ac; 50 Hz or 60 Hz; 3.3 A
Input kilovolt-amperes (kVA) (approximately):
Models with -48Vdc 900 W power supplies:
-48 - -60 (nominal) V dc; 25.8 A
Input kilovolt-amperes (kVA) (approximately):
BTU output:
Minimum configuration: 461 Btu/hr (135 watts)
Maximum configuration: 6667 Btu/hr (1954 watts)
Acoustics:
6.6 bels (operating)
6.4 bels (idle)
Vibration:
Operating: 0.21 G rms at 5 Hz to 500 Hz for 15 minutes across 3 axes
Non-operating: 1.04 G rms at 2 Hz to 200 Hz for 15 minutes across 6 surfaces
Shock:
Operating: 15 G for 3 milliseconds in each direction (positive and negative X, Y, and Z axes)
Non-operating:
12 kg - 22 kg: 50 G for 152 in./sec velocity change across 6 surfaces
23 kg - 31 kg: 35 G for 152 in./sec velocity change across 6 surfaces
Warranty
The System x3550 M5 has a three-year customer-replaceable unit (CRU) and onsite (for field-replaceable
units [FRUs] only) limited warranty with standard call center support during normal business hours and 9x5
Next Business Day Parts Delivered. Also available are Lenovo Services warranty maintenance upgrades and
post-warranty maintenance agreements, with a well-defined scope of services, including service hours,
response time, term of service, and service agreement terms and conditions.
Lenovo System x3550 M5 (Machine Type 8869)
Minimum configuration: 0.14 kVA
Maximum configuration: 1.967 kVA
Minimum configuration: 0.14 kVA
Maximum configuration: 1.194 kVA
Minimum configuration: 0.14 kVA
Maximum configuration: 1.015 kVA
Minimum configuration: 0.14 kVA
Maximum configuration: 0.965 kVA
Minimum configuration: 0.14 kVA
Maximum configuration: 0.732 kVA
Minimum configuration: 0.14 kVA
Maximum configuration: 1.237 kVA
49