ABB REM615 ANSI Product Manual page 27

Relion 615 series. motor protection and control
Hide thumbs Also See for REM615 ANSI:
Table of Contents

Advertisement

ABB
Motor Protection
REM615 ANSI
Product Version 2.0
Table 43. Negative phase-sequence current protection (46) main settings
Parameter
Pickup range
Time multiplier
Defi nite time delay
1)
Operating curve type
1)
For further reference please refer to the Operating characteristics table at the end of the Technical data chapter
Table 44. Loss of load supervision (37)
Characteristic
Operation Accuracy
Start time
Reset time
Reset ratio
Retardation time
Operate time accuracy in defi nite time mode
Table 45. Loss of load supervision (37) main settings
Parameter
Start value high
Start value low
Operate delay time
Operation
Table 46. Motor load jam protection (51LR)
Characteristic
Operation Accuracy
Reset time
Reset ratio
Retardation time
Operate time accuracy in defi nite time mode
Table 47. Motor load jam protection (51LR) main settings
Parameter
Operation
Start value
Operate delay time
Function
Value (Range)
46
0.01...5.00 x I
46
0.05...15.00
46
40...200000 ms
46
Defi nite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13,
14, 15, 17, 18, 19
Value
Depending on the frequency of the current
measured: f
±2Hz
n
±1.5% of the set value or ±0.002 x I
Typical 300 ms
< 40 ms
Typical 0.96
< 35 ms
±1.0% of the set value or ±20 ms
Function
Value (Range)
37
0.01...1.00 x I
37
0.01...0.50 x I
37
40...600000 ms
37
Off
On
Value
Depending on the frequency of the current
measured: f
±2Hz
n
±1.5% of the set value or ±0.002 x I
< 40 ms
Typical 0.96
< 35 ms
±1.0% of the set value or ±20 ms
Function
Value (Range)
51LR
Off
On
51LR
0.01...10.00 x I
51LR
100...120000 ms
1MAC251744 -PG Rev. A
Issued: 03.01.2010
Step
0.01
n
0.05
10
n
Step
0.01
n
0.01
n
10
-
n
Step
-
0.01
n
10
27