Table 19. Electromagnetic compatibility tests
Th e EMC immunity test level meets the requirements listed below:
Description
1 MHz burst disturbance test, class III:
• Common mode
• Diff erential mode
Electrostatic discharge test
• Contact discharge
• Air discharge
Radio frequency interference tests:
• Conducted, common mode
• Radiated, amplitude-modulated
• Radiated, pulse-modulated
Fast transient disturbance tests:
• Signal outputs, binary inputs, IRF
• Other ports
Surge immunity test:
• Binary inputs
• Communication
• Other ports
Power frequency (50 Hz) magnetic fi eld:
• Continuous
Power frequency immunity test:
• Common mode
• Diff erential mode
Voltage dips and short interruptions
18
Type test value
Reference
According to IEC 61000-4-18 and
IEC 60255-22-1, level 3
2.5 kV
1.0 kV
According to IEC 61000-4-2,
IEC 60255-22-2, level 3
6 kV
8 kV
10 V (emf ), f = 150
According to IEC 61000-4-6 and
kHz...80 MHz
IEC 60255-22-6, level 3
10 V/m (rms),
According to IEC 61000-4-3 and
f=80...1000 MHz and
IEC 60255-22-3, level 3
f=1.4...2.7 GHz
According to the ENV 50204 and
10 V/m, f=900 MHz
IEC 60255-22-3, level 3
According to IEC 61000-4-4 and
IEC 60255-22-4, class B
2 kV
4 kV
According to IEC 61000-4-5 and
IEC 60255-22-5, level 4/3
2 kV, line-to-earth
1kV, line-to-line
1 kV, line-to-earth
4 kV, line-to-earth
2 kV, line-to-line
According to IEC 61000-4-8, level 5
300 A/m
According to IEC 60255-22-7, class
A
300 V rms
150 V rms
30%/10 ms
According to IEC 61000-4-11
60%/100 ms
60%/1000 ms
>95%/5000 ms
1MAC251744 -PG Rev. A