Alpha ATS-216 Operating Manual page 6

Automated transfer switch
Table of Contents

Advertisement

3.3.4. Interface
The ATS provides three communication ports and one external
communication slot (optional) for the user.
Standard communication ports: RS-232, USB, and 5 dry contacts
External communication slot: SNMP, RS-485
3.3.4.1. RS-232
3.3.4.2. USB
Pin
Definition
Type
1
N/A
N/A
2
TX
Output
3
RX
Input
4
N/A
N/A
Power
5
GND
source
Power
6
+12V
source
7
N/A
N/A
8
N/A
N/A
9
N/A
N/A
Pin
Signal
1
VBUS
2
D-
3
D+
4
GND
8
3.3.4.3. Dry Contact
The ATS provides five user configurable dry contacts for customized
features. The capacity of each contact is 24Vdc/1A, additional information is
provided in Appendix A.
Signal
N/A
TX
RX
N/A
N/A
N/A
N/A
N/A
N/A
Pin
Definition
Signal (default)
1
Common 3
N/A
2
Relay 3
System Alarm
3
Relay 4
Overload
4
Common
N/A
5
Relay 5
Over temperature
6
Common 1
N/A
7
Relay 1
Source A abnormal
8
Common 2
N/A
9
Relay 2
Source B abnormal
9