2. Piping Design

(1) PUHY-P250 Piping
OU
L1
A
Fig. 2-(1)-A Piping scheme
Table2-(1)-1. Piping length
Item
Farthest IU from OU (L1)
Height between OU and IU (OU above IU)
Height between OU and IU (OU under IU)
OU: Outdoor Unit, IU: Indoor Unit
Table2-(1)-2. Bent equivalent length "M"
Outdoor Model
M (m/bent [ft./bent])
PUHY-P250
0.42 [1.38]
Table2-(1)-3. Piping "A" size selection rule
Outdoor
PUHY-P250=CMY-Y102L-G2
*1. A>=90m [295ft.], ø12.70mm [1/2in.]
Table2-(1)-4. Indoor unit piping size selection rule
Indoor Unit size
P250, P300-F *2
*2. "-F" indicates Fresh air intake type
Note1. If the A/C system is designed to use cooling mode under outdoor temperature 0˚C, H'<=15m.
Note2. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better;
Piping length needs to consider the actual length and equivalent length which bents are counted.
Equivalent piping length (m)=Actual piping length+"M" x Quantity of bent.
IU
IU : Indoor unit , OU : Outdoor unit
Piping in the figure
Max. length
A
165 [541']
H
50 [164']
H'
40 [131']
(mm [in.])
Pipe(Liquid)
Pipe(Gas)
ø9.52 [3/8"] *1
ø22.20 [7/8"]
(mm [in.])
Pipe(Liquid)
Pipe(Gas)
ø9.52 [3/8"]
ø22.20 [7/8"]
82
(m [ft.])
Max. equivalent length
190 [623']
-
-