Common setting

• Function Code 02 : Disable 3 minute delay
Factory use only.
• Function Code 03 : Remote air sensor connection
If user connects remote air sensor to control the unit by room air temperature, the connection
information should be notified to the unit.
Note : If remote air sensor is connected but this function code is not set correctly, the unit can not
be controlled by room air temperature.
• Function Code 04 : Celsius / Fahrenheit switching
Temperature is displayed in Celsius or Fahrenheit.
• Function Code 05 : Setting temperature selection
The unit can be operated according to air temperature or leaving water temperature. The selection
for setting temperature as air temperature or leaving water temperature is determined.
Note : Air temperature as setting temperature is ONLY available when remote air sensor
connection is enabled and Function Code 03 is set as 02.
• Function Code 06 : Auto dry contact
This function allows the dry contact operate under auto run mode or manual mode with remote
controller.
If thermostat is used, value should be changed from "2" to "1".
• Function Code 07 : Address setting
When central controller is installed, address assigning is set by this function.
System Set-Up
Installation Manual 53