Varmebaronen Viking Bio 35 Installation And Maintenance Manual

Pellet burner

Advertisement

Quick Links

1 3 0 6 0 3 T H L n o . : 0 1 r e v 0
Installation and maintenance
Viking Bio 35 - pellet burner

Advertisement

Table of Contents
loading

Summary of Contents for Varmebaronen Viking Bio 35

  • Page 1 1 3 0 6 0 3 T H L n o . : 0 1 r e v 0 Installation and maintenance Viking Bio 35 - pellet burner...
  • Page 2: Table Of Contents

    Position of grate Resetting the alarm Feed auger Temperature sensor’s resistance Flue gas temperature Troubleshooting ..............20 Turbulators Components ..............21 Combustion Adjustment ...............13 Pellet firing ...............14 Pellet quality Handling and storing pellets Combustion Flue gas temperature Turbulators Värmebaronen Viking Bio 35...
  • Page 3: Notes

    Notes To be completed by the installation engineer when the Viking Bio 35 is installed. Add a printout from the flue gas analysis instrument. Serial number: ............................Installation date: ............................Installed in boiler, make/type/power: ............................Installation engineer: ............................Tel.: ............................
  • Page 4: Safety And Handling

    Children may not play with the burner and connected The Viking Bio 35 is designed to fire 6 or 8 mm wood accessories. pellets after it has been installed on a boiler in a boiler room that meets the standards of the Swedish National Board of Housing, Building and Planning.
  • Page 5: Operation - Technical Data

    Operation - Technical data The Viking Bio 35 is a forward-burning pellet burner for wood Different operating modes can be selected: high power, low pellets. power or two power stages. Fuel and air are mixed in a controlled fashion in the burner.
  • Page 6: Installation

    Check that the burner is tight against the damper that is appropriate for the chimney. silicone gasket on the burner flange. The combustion is affected by the draught. Therefore, stable draught conditions are the objective. Värmebaronen Viking Bio 35...
  • Page 7: Downpipe

    This makes it easy to see whether the feed auger has worked its way into the store and it becomes easier to refit the feed auger when it has been taken out of a full store. Värmebaronen Viking Bio 35...
  • Page 8: Electrical Connection

    Black, supply via overheating protection. BROWN Brown, connected to the boiler thermostat. GRAY ALARM 230V/1A Grey, alarm signal, 230 V~, from burner, max. load 1 A. T1, T2: To any safety switch on the combustion chamber hatch. SAFETY SWITCH Värmebaronen Viking Bio 35...
  • Page 9: Electrical Installation

    Subsequently, only ‘OPERATION’ should light up. 3. Turn the thermostat so that it requires heat; the ‘FLAME’ indicator should start to flash. If this does not happen, the connection must be checked. Värmebaronen Viking Bio 35...
  • Page 10: Wiring Diagram

    7. Ignition element Disconnect the plug before service or if the burner is removed from the boiler. 8. Current transformer. 9. Power supply unit, 230 VAC/24 VDC, to supply the electronics and fan motor. Värmebaronen Viking Bio 35...
  • Page 11: Indicators And Settings

    Two power modes OFF (SW1/1) switch from 22 to 35 kW when the OFF(SW1/2) index burner has burned at 22 kW for 20 min. Low power, 22 kW ON (SW1/1) OFF(SW1/2) High power, 35 kW OFF(SW1/1) ON (SW1/2) Värmebaronen Viking Bio 35...
  • Page 12: Startup

    5-10 litres of pellets pass through. CO content: <300 content, mean: 12,5 ± 2,5 When the burner is in operation, the feed auger’s Efficiency: >90 plug, the power supply, must never be removed from the burner! Värmebaronen Viking Bio 35...
  • Page 13: Adjustment

    Perform a CO measurement. firing. Fuel green If the CO value is: - too low: increase ‘Fuel’. Adjustment has now been completed. Refit the burner’s - too high: reduce ‘Fuel’. cover. Repeat this test several times. Värmebaronen Viking Bio 35...
  • Page 14: Pellet Firing

    The correct adjustment is important for reliability, heating is obtained. economy, efficiency and emission levels of environmentally harmful substances. Värmebaronen Viking Bio 35...
  • Page 15: Pellet Firing

    A lower power for the burner results in a longer operating action. time and lower stoppage losses, which produces higher boiler efficiency. The system must always have an alternative energy source to reduce vulnerability. Värmebaronen Viking Bio 35...
  • Page 16: Operation, Start To Stop

    High ambient temperature ---- ••• on the power set. Fan inoperative ---- •••• Home Elements inoperative •••••••• If the flame disappears during this phase, the control switches to the start phase but no pellets will be supplied. Värmebaronen Viking Bio 35...
  • Page 17: Operation And Maintenance

    Ensure that children are unable to enter the store. smouldering. Naked flames are prohibited near the store. Ash must be stored in an ash bucket made of sheet metal with a tight lid. The bucket must be placed on non-flammable material. Värmebaronen Viking Bio 35...
  • Page 18: Safety System

    Disconnect the plug before service or if the replace it with a new burner is removed from the boiler. one. Ignition element Refit in reverse order. Värmebaronen Viking Bio 35...
  • Page 19: Troubleshooting

    If this is not the case, check the inclination of Switch off the power to the burner and detach the feed auger and its insertion into the pellet store. the plug before cleaning or service or before the burner is detached from the boiler. Värmebaronen Viking Bio 35...
  • Page 20: Troubleshooting

    High ----- Low ---- • Decay ----- •• PREPARE Start phase ••• Low ---- ALARM High temperature in downpipe ---- Screw Motor ---- • Startup failure ---- •• High ambient temperature ---- ••• Fan inoperative ---- •••• Home Elements inoperative •••••••• Värmebaronen Viking Bio 35...
  • Page 21: Components

    56 711605 Bracket, inner, complete 1 31 210019 Circuit board 100520 Hook screw 57 711618 Shaft 32 160001 Terminal block, 380030 Flue gas thermometer 58 720457 Insulation protection triple-pole 59 440212 Eccentric lock 160006 End plate, terminal block Värmebaronen Viking Bio 35...
  • Page 22 Draught damper 150 x 130 mm, for flue pipe 90351 (standard VB wood-fired boilers) 2924 Draught damper for cleaning hatch in chimney b: 132 mm 2925 Draught damper large, with adapter 2926 Värmebaronen Viking Bio 35...
  • Page 24 Varmebaronen UK 11 Back O'Hill, Stirling. FK8 1SH Tel. 01786 849 099 Fax 01786 849 098 www.varmebaronen.org info@varmebaronen.org...

Table of Contents