Sanitary Water Tank And Sanitary Water Tank Kit - LG ARNH08GK3A2 Installation Manual

Hydro kit
Hide thumbs Also See for ARNH08GK3A2:
Table of Contents

Advertisement

Installation
Strainer
- Use the 50 mesh strainer.
(Exclude scale diameter of 0.4mm or less and other net)
- Check the strainer direction and assemble on the inlet hole (Refer to picture)
- Wrap the Teflon tape on the screw thread of the water pipe for more than 15 times for assembly.
- Install the service port facing downward. (Within left/right 45 degrees)
- Check if there is any leakage on the connecting part.
- Clean the strainer periodically. (Once a year or more frequent)

Sanitary Water Tank and Sanitary Water Tank Kit

Installation Condition
Installing sanitary water tank requires following considerations :
• Sanitary water tank should be located at the flat place.
• Water quality should comply with EN 98/83 EC Directives.
• As this water tank is sanitary water tank (indirect heat exchange), do not use anti water-freezing
treatment like ethylene grycol.
• It is highly recommend to wash out inside of the sanitary water tank after installation. It ensures
generating clean hot water.
• Near the sanitary water tank, there should be water supply and water drain for easy access and
maintenance.
14 Hydro Kit
Front
Water Tank
Temperature Sensor
Water Out
Water In
Water In
Strainer
Side
Sanitary
Water Tank

Hide quick links: