4) Setting the heater room temperature correction
Depending on the installed environment, the room temperature sensor may require a correction. The settings may be changed as
shown in the table below.
Setting Description
Standard
Lower control
Slightly warmer control
Warmer control
5) Auto restart
Enable or disable automatic system restart after a power outage.
Setting Description
Yes
No
* Auto restart is an emergency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation.
Be sure to operate by the control unit, or external input device.
6) Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when using the control by Wired remote controller temperature sensor.
Setting Description
No
Yes
* If setting value is "00":
Room temperature is controlled by the indoor unit temperature sensor.
* If setting value is "01":
Room temperature is controlled by either indoor unit temperature sensor or remote controller unit sensor.
7) Cool air prevention
This setting is used to set the fan speed when the compressor stops once the room temperature has reached the set temperature during
heating operation.
Setting Description
Super low
Follow the setting on
the remote controller
(corresponding to
ventilation)
8) Remote controller signal code
Change the indoor unit Signal Code, depending on the remote controllers.
Setting Description
A
B
C
D
9) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
Setting Description
Operation/Stop mode
(Setting forbidden)
Forced stop mode
(  . . .Factory setting)
Function Number
Setting Value
00
01
31
02
03
(  . . .Factory setting)
Function Number
Setting Value
00
40
01
(  . . .Factory setting)
Function Number
Setting Value
00
42
01
(  . . .Factory setting)
Function Number
Setting Value
00
43
01
(  . . .Factory setting)
Function Number
Setting Value
00
01
44
02
03
(  . . .Factory setting)
Function Number
Setting Value
00
46
01
02
- (01 - 32) -