(5) Press the TIMER SET button to confirm the setting. Press the TIMER SET button for a few seconds until the setting value stops
flashing. If the setting value display changes or if "- -" is displayed when the flashing stops, the setting value has not been set correctly.
(An invalid setting value may have been selected for the indoor unit.)
(6) Repeat steps 2 to 5 to perform additional settings. Press the SET TEMP. buttons (
more than 5 seconds to cancel the function setting mode. In addition, the function setting mode will be automatically canceled after 1
minute if no operation is performed.
(7) After completing the FUNCTION SETTING, be sure to turn off the power and turn it on again.
• After turning off the power, wait 30 seconds or more before turning on it again. The Function Setting will not become active
unless the power is turned off then on again.
CONTENTS OF FUNCTION SETTING
• Follow the instructions in the Local Setup Procedure, which is supplied with the remote control, in accordance with the installed
condition.
After the power is turned on, perform the Function Setting on the remote control.
• The settings may be selected between the following two: Function Number or Setting Value.
• Settings will not be changed if invalid numbers or setting values are selected.
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
11)
1) Filter sign
The indoor unit has a sign to inform the user that it is time to clean the filter. Select the time setting for the filter sign display interval in
the table below according to the amount of dust or debris in the room. If you do not wish the filter sign to be displayed, select the setting
value for "No indication".
Setting Description
Standard (2500 hours)
Long interval (4400 hours)
Short interval (1250 hours)
No indication
2) Setting the static pressure
Select appropriate static pressure according to the installation conditions.
Refer to the technical manual for details or follow the instructions of the duct designer.
Setting Description
Normal
High static pressure 1
High static pressure 2
High static pressure 3
3) Setting the cooler room temperature correction
Depending on the installed environment, the room temperature sensor may require a correction. The settings may be selected as shown
in the table below.
Setting Description
Standard
Slightly lower control
Lower control
Warmer control
!
CAUTION
Filter sign
Static pressure
Cooler room temperature correction
Heater room temperature correction
Auto restart
Indoor room temperature sensor switching function
Cool air prevention
Remote controller signal code
External input control
Room temperature control switching
Indoor unit fan control for energy saving
(  . . .Factory setting)
Function Number
Setting Value
11
(  . . .Factory setting)
Function Number
Setting Value
21
(  . . .Factory setting)
Function Number
Setting Value
30
- (01 - 31) -
) (
) and FAN button simultaneously again for
00
01
02
03
00
01
02
03
00
01
02
03