Attach The Intake Grille; Test Operation; Test Operation Using Pcb (Outdoor Unit); Test Operation Using Remote Controller - Fujitsu AUXB07L Installation Manual

Vrf system indoor unit compact cassette type
Hide thumbs Also See for AUXB07L:
Table of Contents

Advertisement

(3) Attach the connector cover.
Screw

8.3. Attach the intake grille

The installation is the reverse of "REMOVING THE INTAKE
GRILLE".
The intake grille can be rotated and installed 4 ways to suit
the user's preference.
CAUTION
• The louver angle cannot be changed if the power is not on, (If
moved by hand, it may be damaged.)
• The grille assembly is directional relative to the air
conditioner body.
• Install so that there is no gap between the grille assembly
and the air conditioner body.

9. TEST OPERATION

9.1.Test operation using PCB (Outdoor unit)

• Refer to the Installation Manual for the outdoor unit if
the PCB for the outdoor unit is to be used for the test
operation.

9.2. Test operation using Remote Controller

• Refer to the Installation Manual for the remote control unit
to perform the test operation using the wireless remote
control unit.
• When the air conditioner is being test run, the OPERATION
and TIMER indicator lamps flash slowly at the same time.
Connector cover

10. CHECK LIST

Pay special attention to the check items below when
installing the indoor unit(s). After installation is complete, be
sure to check the following check items again.
CHECK ITEMS
Has the indoor unit been
installed correctly?
Has there been a check
for gas leaks (refrigerant
pipes)?
Has heat insulation work
been completed?
Does water drain easily
from the indoor units?
Is the voltage of the
power source the same
as that indicated on the
label on the indoor unit?
Are the wires and pipes
all connected completely?
Is the indoor unit
grounded?
Is the connection cable
the specified thickness?
Are the inlets and outlets
free of any obstacles?
After installation is
completed, has the proper
operation and handling
been explained to the
user?
If not performed
CHECK
correctly
BOX
Vibration, noise,
indoor unit may drop
No cooling, No heating
Water leakage
Water leakage
No operation, heat or
burn damage
No operation, heat or
burn damage
Short circuit
No operation, heat or
burn damage
No cooling, No heating
En-17

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

Auxb24l

Table of Contents