Fujitsu AUXB07L Installation Manual page 11

Vrf system indoor unit compact cassette type
Hide thumbs Also See for AUXB07L:
Table of Contents

Advertisement

Screw with
special washer
Cable end
(Loop)
Cable
Terminal block
• When using solid core cables, do not use the ring terminal. If
you use the solid core cables with the ring terminal, the ring
terminal's pressure bonding may malfunction and cause the
cables to abnormally heat up.
B. For strand wiring
(1) Use ring terminals with insulating sleeves as shown in the
figure below to connect to the terminal block.
(2) Securely clamp the ring terminals to the cables using an
appropriate tool so that the cables do not come loose.
(3) Use the specified cables, connect them securely, and fasten
them so that there is no stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws.
Do not use a screwdriver that is too small, otherwise, the screw
heads may be damaged and prevent the screws from being
properly tightened.
(5) Do not tighten the terminal screws too much, otherwise, the
screws may break.
(6) See the table for the terminal screw tightening torques.
(7) Please do not fix two power supply cables with one screw.
Screw with
special washer
Ring terminal
Cable
Terminal block
Loop
Screw with
special washer
Cable end
(Loop)
Cable
WARNING
Ring terminal
Sleeve
Screw with
special washer
Ring
terminal
Cable
WARNING
• Use ring terminals and tighten the terminal screws to the
specified torques, otherwise, abnormal overheating may be
produced and possibly cause heavy damage inside the unit.
Tightening torque
M4 screw
(Power supply /L, N, GND)
6.3.2. Transmission and Remote control cable
Shielded
cable (no film)
Transmission
Remote control
• Connect remote control and transmission cables as shown
in Fig. C.
Fig. C
Different
diameter
OK
NO GOOD
WARNING
• Tighten the terminal screws to the specified torques,
otherwise, abnormal overheating may be produced and
possibly cause heavy damage inside the unit.
Tightening torque
M3 screw
(Transmission /X1, X2)
(Remote control /Y1, Y2, Y3)
CAUTION
• To peel the film from the lead cable, use a dedicated tool that
will not damage the conductor cable.
• When installing a screw on the terminal block, do not cut
the wire by overtightening the screw. On the other hand, an
undertightened screw can cause faulty contact, which will
lead to a communication failure.
1.2 to 1.8N
m
(12 to 18 kgf
cm)
cable
cable
Connect to
one side
NO GOOD
0.5 to 0.6N
m
(5 to 6 kgf
cm)
En-11

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

Auxb24l